Skip to main content

Event Notification Report for March 04, 2002

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/03/2002 - 03/04/2002

EVENT NUMBERS
3874838749

Power Reactor
Event Number: 38748
Facility: MCGUIRE
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: PHILLIP THOMPSON
HQ OPS Officer: MIKE NORRIS
Notification Date: 03/04/2002
Notification Time: 10:13 [ET]
Event Date: 03/04/2002
Event Time: 08:41 [EST]
Last Update Date: 03/04/2002
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iv)(B) - RPS ACTUATION - CRITICAL 50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
CAUDLE JULIAN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO LOSS OF FEEDWATER

"Manual reactor trip due to falling level in 1A Steam Generator (S/G), (RPS Activation). Level decrease occurred after the Feedwater Regulating Valve (FRV) for the 1A S/G failed closed upon loss of the normal and backup electrical power to the valve solenoid. After the reactor trip, the 1A S/G experienced a LO-LO Level Alarm which auto started both motor driven Auxiliary Feedwater pumps, (ESF Actuation). All S/G levels are now at normal levels and Unit 1 is stable. An investigation is in progress to determine the loss of electrical power to the FRV solenoid for the 1A S/G."

The plant is dumping steam to the Main Condenser with no known Primary/Secondary leakage. There was no actuation of primary safety valves. All safety systems are operable and normal electrical distribution is available.

The NRC Resident Inspector has been notified.


Power Reactor
Event Number: 38749
Facility: POINT BEACH
Region: 3     State: WI
Unit: [1] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: RICK ROBBINS
HQ OPS Officer: GERRY WAIG
Notification Date: 03/04/2002
Notification Time: 11:37 [ET]
Event Date: 03/04/2002
Event Time: 00:00 [CST]
Last Update Date: 03/04/2002
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a) (1) (i) - EMERGENCY DECLARED
Person (Organization):
JOHN MADERA (R3)
CHRIS GRIMES (EO)
RICHARD WESSMAN (IRO)
JEFF GRANT (R3)
REGION V OSC (EPA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT DUE TO UNCONTROLLED FLAMMABLE GAS LEAK ONSITE

At 0946 CST, 3/4/02, an Unusual Event was declared due to a non isolable leak on a propane tank. The tank is approximately 500 to 750 gals, and is 55 % full. The tank is leaking at the rate of 5% decrease every 20 minutes. The tank is 25 to 30 yards out in the Owner Controlled Area and a local area evacuation has been performed. The Two Creek Fire Department is on the scene.

NRC Resident Inspector has been notified.

At 1147 EST, NRC entered Monitoring for Normal Phase Mode.

***EVENT UPDATED AT 1309 EST ON 3/4/02 BY MARK HANSON TO FANGIE JONES***

At 1154 CST, Licensee terminated Unusual Event due to leak isolated.

At 1310 EST, NRC exited monitoring for the Unusual Event.

Notified IRO (Holonich), R3DO (Madera), NRR (Grimes), PAO (Dricks), FEMA (Snyder).