Skip to main content

Event Notification Report for October 05, 2001

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
10/04/2001 - 10/05/2001

EVENT NUMBERS
3835938352383533835638357

Hospital
Event Number: 38359
Rep Org: RESEARCH MEDICAL CENTER
Licensee: RESEARCH MEDICAL CENTER
Region: 3
City: KANSAS CITY   State: MO
County: JACKSON
License #: 24-18625-01
Agreement: N
Docket:
NRC Notified By: STEVEN SLACK
HQ OPS Officer: LEIGH TROCINE
Notification Date: 10/05/2001
Notification Time: 17:34 [ET]
Event Date: 10/05/2001
Event Time: 10:30 [CDT]
Last Update Date: 10/05/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
35.33 - MED MISADMINISTRATION
Person (Organization):
DAVID HILLS (R3)
PATRICIA HOLAHAN (NMSS)
Event Text
MEDICAL MISADMINISTRATION INVOLVING A MISSING IRIDIUM-192 SEED

At 0830 CDT on 10/05/01, the licensee discovered that 1 of 71 iridium-192 seeds was missing following a brachytherapy treatment involving both cesium-137 tubes and iridium-192 ribbons. The licensee's investigation revealed that the missing iridium-192 seed remained inside the patient. The licensee determined that this event was reportable at 1030 CDT on 10/05/01.

The patient was in surgery at the time of this event notification. As a result, the total dose the patient has not yet been determined. The missing iridium-192 seed had an activity of 0.89 millicuries.

***** UPDATE FROM STEVEN SLACK TO LEIGH TROCINE AT 1819 EDT ON 10/05/01 *****

The missing iridium-129 seed was successfully recovered at 1645 CDT on 10/05/01.

The NRC operations officer notified the R3DO (David Hills) and NMSS EO (Patricia Holahan).


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 38352
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: J. A. WITTER
HQ OPS Officer: STEVE SANDIN
Notification Date: 10/05/2001
Notification Time: 04:30 [ET]
Event Date: 10/05/2001
Event Time: 00:26 [EDT]
Last Update Date: 12/05/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(B) - POT RHR INOP
Person (Organization):
RICHARD CONTE (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
UNIT 2 ENTERED TECH SPEC 3.0.3 DUE TO TWO TRAINS OF SERVICE WATER DECLARED INOPERABLE

"At 0026 hrs on October 5, 2001, Beaver Valley Power Station Unit 2 experienced a trip of the 'A' Train Service Water (SWS) Pump. 2SWS-P21 C was operating on the 'A' SWS header when the pump tripped on Motor Ground Over Current. Both A and B Train Emergency Service Water Pumps (SWE) auto started as designed and Service Water header pressure returned to normal values. Due to a piping class break, safety/non-safety, between the SWS and SWE systems, the unit entered Technical Specification 3.0.3 due to two trains of Service Water being Inoperable. The unit entered and completed the Abnormal Operating Procedure for Loss of Service Water, and the Bravo Train of Service Water was restored Operable when 2SWE-P21 B was secured and isolated from the 'B' SWS header. 25W5-P21 B continued to operate normally during this event. Technical Specification 3.0.3 was exited at 0037 hrs. The plant is currently stable and operating at 100% power. Technical Specification 3.7.4.1 for Service Water (72-hour action) is applicable, as the only operating pump on the 'A' SWS header is 2SWE-P21A. The Alpha Service Water Pump, 2SWS-P21 A is unavailable due to Intake Structure Bay cleaning. Currently efforts are under way to recover the Intake Bay and restore 2SWS-P21A Operable. It is expected that both trains of Service Water will be Operable within 12 hours. The Non Safety Related Chiller units tripped due to the SWS low pressure conditions, and were recovered shortly there after. No additional failures or equipment challenges occurred as a result of this event."

The licensee informed the NRC resident inspector.

* * * RETRACTED AT 1907 EST ON 12/5/01 BY J. A. WITTER TO FANGIE JONES * * *

"At 0430 hours on October 5, 2001 Beaver Valley Power Station Unit 2 reported entry into Technical Specification 3.0.3, due to two trains of the Service Water System being inoperable (Event Notification #38352). The declaration of the loss of both trains of the Service Water System was a conservative action taken by the operating personnel at that time. This notification is a retraction of the 10 CFR 50.72(b)(3)(v)(B) event on October 5, 2001 at 0026 hours. Subsequent investigation of the event and engineering assessment of operability concluded that one train of the Service Water System remained operable throughout the time period of this event. Therefore, Technical Specification 3.0.3 was not applicable and Technical Specification 3.7.4.1 was applicable for the loss of one train of Service Water, which was subsequently properly exited 6 hours later."

The licensee notified the NRC Resident Inspector. The R1DO (John Rogge) has been notified.


General Information or Other
Event Number: 38353
Rep Org: ABB INC.
Licensee: ABB INC.
Region: 0
City:   State:
County:
License #:
Agreement: N
Docket:
NRC Notified By: RUSS GONNAM
HQ OPS Officer: FANGIE JONES
Notification Date: 10/05/2001
Notification Time: 14:26 [ET]
Event Date: 10/05/2001
Event Time: 00:00 [EST]
Last Update Date: 10/05/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
21.21 - UNSPECIFIED PARAGRAPH
Person (Organization):
VERN HODGE (FAX) (NRR)
RICHARD CONTE (R1)
FRANK JAPE (R2)
DAVID HILLS (R3)
CLAUDE JOHNSON (R4)
Event Text
10 CFR PART 21 REPORT CONCERNING A CLASS 1E RELAY

The following is the faxed report:

Subject: Initial Notification of Potential Defect per 10 CFR Part 21 Type CVE/CVE-1 Relays

Provided By: ABB Inc., Substation Automation & Protection Division

This letter is the initial notification of a deviation concerning our Class 1E relay type CVE/CVE-1. The deviation concerns the difference between the original zero period acceleration value and the recent zero period acceleration value as reported to us by an independent dedicating entity.

Details will be provided in our written notification forthcoming within the next thirty days.


Power Reactor
Event Number: 38356
Facility: CLINTON
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: ED TIEDEMANN
HQ OPS Officer: FANGIE JONES
Notification Date: 10/05/2001
Notification Time: 17:11 [ET]
Event Date: 10/05/2001
Event Time: 00:00 [CDT]
Last Update Date: 10/05/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
DAVID HILLS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 99 Power Operation
Event Text
24-HOUR REPORT IN ACCORDANCE WITH OPERATING LICENSE DUE TO POTENTIAL MAXIMUM POWER LEVEL VIOLATION

"This report is being made in accordance with Clinton Power Station Unit #1 Operating License Condition #2.G as a potential violation of License Condition #2.C(1), Maximum Power Level.

"GE Report titled 'Impact of Steam Carryover Fraction on Process Computer Heat Balance Calculations', September 2001, documents a non-conservative assumption for the moisture carryover fraction used in the calculation of core thermal power. The assumed carryover fraction of 0.1 % was discovered to be potentially closer to zero and therefore non-conservative in later model GE BWRs.

"A review of Clinton Power Station Unit #1 moisture carryover test data performed on May 21 2001 found a moisture carryover value of 0.0046% and on October 4, 2001 found a moisture carryover value of 0.0020% inducing an estimated bias of approximately 2.4 MWth. Based on this potential non-conservatism on Unit #1 indicated Maximum Power Level shift average is being administratively controlled 4 MWth below the licensed power level of 2894 MWth.

"Exelon staff is continuing to evaluate the effect of the moisture carryover term in the heat balance calculation. The NRC resident has been notified."

(Refer to event numbers 38330, 38337, 38340, 38344, 38445, 38347, 38349, and 38357 for similar events at Fermi, Perry, Hope Creek, Grand Gulf, Columbia Generating Station, Limerick 2, River Bend, and Limerick 1.)


Power Reactor
Event Number: 38357
Facility: LIMERICK
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: PETER M. ORPHANOS
HQ OPS Officer: LEIGH TROCINE
Notification Date: 10/05/2001
Notification Time: 17:10 [ET]
Event Date: 10/05/2001
Event Time: 11:15 [EDT]
Last Update Date: 10/05/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
RICHARD CONTE (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
24-HOUR REPORT IN ACCORDANCE WITH OPERATING LICENSE DUE TO POTENTIAL MAXIMUM POWER LEVEL VIOLATION

The following text is a portion of a facsimile received from the licensee.

"This report is being made in accordance with Limerick Generating Station Unit 1 Operating License Condition 2.F as a potential violation of License Condition 2.C(1), Maximum Power Level."

"GE Report titled, 'Impact of Steam Carryover Fraction on Process Computer Heat Balance Calculations,' September 2001, documents a non-conservative assumption for the moisture carryover fraction used in the calculation of core thermal power. The assumed carryover fraction of 0.1% was discovered to be potentially closer to zero and therefore non-conservative in later model GE BWRs."

"A review of Limerick Unit 1 moisture carryover test data performed in September of 1999 found a moisture carryover value of 0.1%. However, it is believed that the results of the test may be more in line with the Limerick Unit 2 data of 0.0277%. This results in an estimated bias of approximately 2.8 MWth Based on this potential non-conservatism on Unit 1, an input parameter of the Process Computer has been changed to eliminate this bias."

'Exelon staff is continuing to evaluate the effect of the moisture carryover term in the heat balance calculation."

The licensee plans to notify the NRC resident inspector.

(Refer to event numbers 38330, 38337, 38340, 38344, 38445, 38347, 38349, and 38356 for similar events at Fermi, Perry, Hope Creek, Grand Gulf, Columbia Generating Station, Limerick 2, River Bend, and Clinton.)