Event Number: 38125
Rep Org: COLORADO DEPT OF HEALTH
Licensee: CTC-GEOTECH
Region: 4
City:   State: CO
County:
License #: CORAM552-01
Agreement: Y
Docket:
NRC Notified By: TIM BONZER
HQ OPS Officer: FANGIE JONES
Notification Date: 07/10/2001
Notification Time: 12:15 [ET]
Event Date: 07/09/2001
Event Time: 00:00 [MDT]
Last Update Date: 07/10/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
CHUCK CAIN (R4)
FREDERICK STURZ (NMSS)
Event Text
AGREEMENT STATE REPORT - STOLEN TROXLER GAUGE

The Colorado Department of Health received a call from CTC-Geotech at approximately 9:30 (AM) on 7/10/01. The call reported a Troxler gauge model 3430 serial #32097 stolen late afternoon on 7/9/01. It was stolen from a job site in Thorton, CO. The gauge was chained to the back of pickup truck and the locks were cut while the user was inside a construction trailer getting work information. A police report and a written report will be sent to Colorado Department of Health.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 38122
Facility: SUMMER
Region: 2     State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: FRED LUCAS
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/09/2001
Notification Time: 07:13 [ET]
Event Date: 07/09/2001
Event Time: 06:30 [EDT]
Last Update Date: 07/09/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
73.71(b)(1) - SAFEGUARDS REPORTS
Person (Organization):
EDWARD MCALPINE (R2)
DAVIDSON, NMSS (IAT)
SKELTON, NRR (IAT)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
ATTEMPTED INTRODUCTION OF CONTRABAND INTO THE PROTECTED AREA BY A LICENSED OPERATOR. IMMEDIATE COMPENSATORY MEASURES TAKEN UPON DISCOVERY.

LICENSEE NOTIFIED THE NRC RESIDENT INSPECTOR.

CONTACT THE HEADQUARTERS OPERATIONS OFFICER FOR FURTHER DETAILS.

* * * RETRACTED AT 1517 EDT ON 7/9/2001 BY SUSAN REESE TO FANGIE JONES * * *

The licensee is retracting this report following further investigation.

The licensee notified the NRC Resident Inspector. The R2DO (Edward McAlpine), NRR IAT (Robert Skelton), and NMSS IAT (Aaron Danis) have been notified.

Contact the Headquarters Operations Officer for further details.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 38123
Facility: CLINTON
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: JAMIE BARTSCH
HQ OPS Officer: FANGIE JONES
Notification Date: 07/09/2001
Notification Time: 13:07 [ET]
Event Date: 07/09/2001
Event Time: 09:00 [CDT]
Last Update Date: 07/13/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(v)(D) - ACCIDENT MITIGATION
Person (Organization):
DAVID HILLS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
CONTROL ROOM VENTILATION SYSTEM DECLARED INOPERABLE

The Division 2 Main Control Room Ventilation System was declared inoperable at 0900 CDT on 7/9/2001 because it was not maintaining the required positive pressure while running in the High Radiation Mode of operation. The system was declared operable at 0913 CDT when the required positive pressure was restored. During the 13 minute period Division 2 was inoperable, Division 1 Main Control Room Ventilation System was inoperable due to a scheduled maintenance outage. Therefore, with both systems inoperable, a condition existed which could have prevented the fulfillment of the safety function of the Main Control Room Ventilation System needed to mitigate the consequences of an accident. The cause of the perturbation in control room pressure is being investigated.

The licensee notified the NRC Resident Inspector.

*** RETRACTION FROM STEVEN STRICKLAN RECEIVED BY LEIGH TROCINE AT 0451 EDT ON 07/13/01 ***

The licensee is retracting this event notification. The following text is a portion of a facsimile received from the licensee:

"On 07/09/01, at approximately 0900 [CDT], the Clinton Power Station (CPS) experienced a transient situation where, for a period of 13 minutes, the positive pressure in the Main Control Room (MCR) was compromised. Based on this condition, an ENS notification (#38123) was made in accordance with the requirements of 10CFR50.72(b)(3)(v), any event or condition that at the time of discovery could have prevented the fulfillment of the safety function of structures or systems that are needed to:
(A) shut down the reactor and maintain it in a safe shutdown condition;
(B) remove residual heat;
(C) control the release of radioactive material; or
(D) mitigate the consequences of an accident."

"An evaluation of the conditions present at the time positive pressurization of the MCR was temporarily interrupted has been performed. The evaluation results indicated that the conditions that potentially existed during this event were bounded by the design basis analysis performed for the [MCR]. The calculated MCR operator thyroid dose for this event was determined to be approximately 23.185 Rem, which is less than the USAR calculated dose of 25 Rem. The USAR dose is calculated based on a 20-minute time delay in starting the system in the high radiation mode. For this event, the high radiation mode was already in operation. Whole body and Beta dose for this event are not governing."

"It [has] therefore been demonstrated that, in the event of a design basis event, time dose impact of the condition as it existed would be bounded by the current analyses of record. As such, the safety function would be fulfilled, and the ENS notification is retracted."

"Although it has been demonstrated that the safety function would be fulfilled, the situation represented a condition prohibited by Technical Specifications, and this event continues to be evaluated for reportability as a Licensee Event Report under 10CFR50.73(a)(2)(i)(B)."

The licensee notified the NRC resident inspector. The NRC operations center notified the R3DO (Hills).