Skip to main content

Event Notification Report for June 02, 2001

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/01/2001 - 06/02/2001

EVENT NUMBERS
3804638047

Fuel Cycle Facility
Event Number: 38046
Facility: PADUCAH GASEOUS DIFFUSION PLANT
Region: 3     State: KY
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: MIKE UNDERWOOD
HQ OPS Officer: FANGIE JONES
Notification Date: 06/02/2001
Notification Time: 14:16 [ET]
Event Date: 06/02/2001
Event Time: 01:55 [CDT]
Last Update Date: 06/02/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MARK RING (R3)
LARRY CAMPER (NMSS)
Event Text
SAFETY SYSTEM ACTUATION

"At 0155 on 06-02-01 the Plant Shift Superintendent (PSS) was notified of an activation of the High Voltage UF6 Release Detection System at the C-315 Tails Withdrawal Building. An Instrument Mechanic was walking down job in preparation for connecting a safety sample buggy to valve SW-53. In order to verify which instrument line was the correct one to connect to the buggy, the mechanic moved the quarter inch copper line. The mechanic reported that the line broke and he saw smoke come from the area. Personnel in the area evacuated to the Area Control Room (ACR) and the Plant Emergency Squad was notified. Subsequent to the release, UF6 Detector heads YE-10-2-6 and YE-10-2-7 alarmed in the ACR. Detector head YE-10-2-6 is a TSR required Q component. The Plant Emergency Squad mitigated the release and the area was turned over to Operations.

"High volume air samples and wipe samples by Health Physics personnel indicate no widespread radiological contamination. Contamination was confined to the immediate area at the broken instrument line. Precautionary urine samples submitted by the two employees near the release indicated fluoride uptakes below plant recall limits of 5 mg/L. Analysis for uranium uptake indicated one employee's results were below detectable limits. The other employee's results indicated an uptake 7.3 µg U/L, which is above the plant recall limit of 5.0 µg U/L but below the restriction limit of 40 µg U/L. A follow-up urinalysis will be performed upon this employee upon his return to work at 1900 hours on 6-2-01.

"This safety system actuation is reportable to the NRC as required by Safety Analysis Report, section 6.9, table 1 criteria J.2, Safety System actuation due to a valid signal as a 24-hour event notification,

"The NRC Resident inspector has been notified of this event.

"PGDP Problem Report No. ATR-01-2653; PGDP Event Report No. PAD-2001-022; Event Worksheet Responsible Division: Operations"


Power Reactor
Event Number: 38047
Facility: SEABROOK
Region: 1     State: NH
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: DENNIS BEMIS
HQ OPS Officer: FANGIE JONES
Notification Date: 06/02/2001
Notification Time: 18:03 [ET]
Event Date: 06/02/2001
Event Time: 15:30 [EDT]
Last Update Date: 06/02/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(xi) - OFFSITE NOTIFICATION
Person (Organization):
ERIC REBER (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION TO STATE

The licensee notified the state public service commission concerning an injured employee who will spend the night in the hospital. A watch stander fell off a ladder. No contamination involved.

The licensee intends to notify the NRC Resident Inspector.