Event Notification Report for June 01, 2001
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
05/31/2001 - 06/01/2001
EVENT NUMBERS
38045
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 38045
Facility: COLUMBIA GENERATING STATION
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: MYRON BAIRD
HQ OPS Officer: FANGIE JONES
Region: 4 State: WA
Unit: [2] [] []
RX Type: [2] GE-5
NRC Notified By: MYRON BAIRD
HQ OPS Officer: FANGIE JONES
Notification Date: 06/01/2001
Notification Time: 19:53 [ET]
Event Date: 06/01/2001
Event Time: 14:02 [PDT]
Last Update Date: 07/12/2001
Notification Time: 19:53 [ET]
Event Date: 06/01/2001
Event Time: 14:02 [PDT]
Last Update Date: 07/12/2001
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
10 CFR Section:
50.72(b)(3)(iv)(A) - VALID SPECIF SYS ACTUATION
Person (Organization):
DALE POWERS (R4)
DALE POWERS (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | N | 0 | Refueling | 0 | Refueling |
INADVERTENT LOSS OF POWER TO A SAFETY BUS
"At 1402 PST, with Columbia Generating Station in Mode 5, a loss of 230 KV offsite source (startup transformer) occurred. This resulted in a loss of voltage to the Div 2 safety related bus (SM-8) which was automatically reenergized by the 115 KV offsite source (backup transformer). All plant systems and components responded as expected. No core alterations were in progress. SM-8 was inoperable but energized at the time of the event due to planned outage maintenance. There was no challenge to the plant shutdown safety plan as a result of this loss of offsite power. The loss of power was a result of a lightning strike offsite on the Bonneville Power Administration (BPA) electrical grid. Restoration of the 230 KV source is pending repairs to damage on the BPA grid. This notification is being made pursuant to 10CFR50.72(b)(3)(iv)(B)(8). This is a valid actuation of an Emergency AC electrical power system."
The licensee notified the NRC Resident Inspector.
* * * RETRACTION 1741 FROM SHERMAN TAKEN BY STRANSKY * * *
"Columbia Generating Station hereby retracts a report made to the NRC Operations Center on June 1st, 2001 at 1953 hours. Event Notification number was 38045. The report was made pursuant to 10 CFR 50.72(b)(3)(iv)(B)(8) and documented that a lightning strike resulted in a loss of a 230kV offsite power line to a safety related electrical bus (SM-8) due to a startup transformer tripping offline. At the time of the event, the plant was already shut down in Mode 5. The safety related electrical bus was automatically reenergized by the backup offsite 115 kV electrical source through the backup transformer.
"It was assumed at the time of the report that a loss of offsite power was an actuation of an emergency AC power system. Upon further review, we have concluded that an automatic bus transfer of offsite power is an alternate normal power supply and not in the scope of NUREG-1022 as an actuation of an emergency AC power source. Our licensing basis documents also refer to the emergency diesel generators as the source of all emergency AC power."
The NRC resident inspector will be informed of this retraction. Notified R4DO (Cain).
"At 1402 PST, with Columbia Generating Station in Mode 5, a loss of 230 KV offsite source (startup transformer) occurred. This resulted in a loss of voltage to the Div 2 safety related bus (SM-8) which was automatically reenergized by the 115 KV offsite source (backup transformer). All plant systems and components responded as expected. No core alterations were in progress. SM-8 was inoperable but energized at the time of the event due to planned outage maintenance. There was no challenge to the plant shutdown safety plan as a result of this loss of offsite power. The loss of power was a result of a lightning strike offsite on the Bonneville Power Administration (BPA) electrical grid. Restoration of the 230 KV source is pending repairs to damage on the BPA grid. This notification is being made pursuant to 10CFR50.72(b)(3)(iv)(B)(8). This is a valid actuation of an Emergency AC electrical power system."
The licensee notified the NRC Resident Inspector.
* * * RETRACTION 1741 FROM SHERMAN TAKEN BY STRANSKY * * *
"Columbia Generating Station hereby retracts a report made to the NRC Operations Center on June 1st, 2001 at 1953 hours. Event Notification number was 38045. The report was made pursuant to 10 CFR 50.72(b)(3)(iv)(B)(8) and documented that a lightning strike resulted in a loss of a 230kV offsite power line to a safety related electrical bus (SM-8) due to a startup transformer tripping offline. At the time of the event, the plant was already shut down in Mode 5. The safety related electrical bus was automatically reenergized by the backup offsite 115 kV electrical source through the backup transformer.
"It was assumed at the time of the report that a loss of offsite power was an actuation of an emergency AC power system. Upon further review, we have concluded that an automatic bus transfer of offsite power is an alternate normal power supply and not in the scope of NUREG-1022 as an actuation of an emergency AC power source. Our licensing basis documents also refer to the emergency diesel generators as the source of all emergency AC power."
The NRC resident inspector will be informed of this retraction. Notified R4DO (Cain).