Event Notification Report for December 21, 2000
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
12/20/2000 - 12/21/2000
Power Reactor
Event Number: 37628
Facility: MONTICELLO
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: BRETT WELER
HQ OPS Officer: CHAUNCEY GOULD
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: BRETT WELER
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 12/21/2000
Notification Time: 11:52 [ET]
Event Date: 12/21/2000
Event Time: 10:40 [CST]
Last Update Date: 12/21/2000
Notification Time: 11:52 [ET]
Event Date: 12/21/2000
Event Time: 10:40 [CST]
Last Update Date: 12/21/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
Person (Organization):
THOMAS KOZAK (R3)
THOMAS KOZAK (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
UNAVAILABILITY OF THE TECHNICAL SUPPORT CENTER (TSC) DURING MAINTENANCE
The following text is a portion of a facsimile received from the licensee:
"Qualitative testing results associated with V-FU-17 (TSC-EVS system) prompted the need to replace the associated charcoal filter elements. During the period of filter element replacement, the TSC-EVS system [was] unavailable. As such, the ability to maintain the TSC as an Emergency Response Facility during an event involving a radioactive release is challenged."
"This constitutes a condition reportable to the NRC per 10CFR50.72 (degradation of [an] Emergency Response Facility)."
Testing is ongoing prior to restoring the TSC to standby mode.
The licensee notified the NRC resident inspector.
The following text is a portion of a facsimile received from the licensee:
"Qualitative testing results associated with V-FU-17 (TSC-EVS system) prompted the need to replace the associated charcoal filter elements. During the period of filter element replacement, the TSC-EVS system [was] unavailable. As such, the ability to maintain the TSC as an Emergency Response Facility during an event involving a radioactive release is challenged."
"This constitutes a condition reportable to the NRC per 10CFR50.72 (degradation of [an] Emergency Response Facility)."
Testing is ongoing prior to restoring the TSC to standby mode.
The licensee notified the NRC resident inspector.
Power Reactor
Event Number: 37629
Facility: NINE MILE POINT
Region: 1 State: NY
Unit: [] [2] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: LANGE
HQ OPS Officer: CHAUNCEY GOULD
Region: 1 State: NY
Unit: [] [2] []
RX Type: [1] GE-2,[2] GE-5
NRC Notified By: LANGE
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 12/21/2000
Notification Time: 12:19 [ET]
Event Date: 12/21/2000
Event Time: 11:50 [EST]
Last Update Date: 12/21/2000
Notification Time: 12:19 [ET]
Event Date: 12/21/2000
Event Time: 11:50 [EST]
Last Update Date: 12/21/2000
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a)(1)(i) - EMERGENCY DECLARED
10 CFR Section:
50.72(a)(1)(i) - EMERGENCY DECLARED
Person (Organization):
ANTHONY DIMITRIADIS (R1)
JOSE CALVO (NRR)
SULLIVAN (FEMA)
FRANK CONGEL (IRO)
TAD MARSH (NRR)
ANTHONY DIMITRIADIS (R1)
JOSE CALVO (NRR)
SULLIVAN (FEMA)
FRANK CONGEL (IRO)
TAD MARSH (NRR)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
PLANT DECLARED AN UNUSUAL EVENT AT 1150 EST DUE TO AN INADVERTENT CARBON DIOXIDE DISCHARGE
An inadvertent (personnel error) discharge in a localized area (switchgear room) of the reactor building occurred. The CO-2 discharge has been stopped, area ventilation is in progress, and all personnel were evacuated and accounted for. The Nine Mile Point 2 Fire Department was activated to help with this problem and is still in the area until the area is ventilated. The NRC Resident Inspector was notified along with the State and local Government and other agencies.
* * * UPDATE ON 12/21/00 @ 1646 BY LANGE TO GOULD * * *
The NOUE was terminated at 1639 following thorough air sampling of the affected areas to check the oxygen levels. The oxygen levels checked good and the NOUE was terminated.
The NRC Resident Inspector was notified along with the State, local and other Government agencies.
The HOO notified FEMA(Cegielski), EO(Marsh), RDO(Dimitriadis), IRO(Congel)
An inadvertent (personnel error) discharge in a localized area (switchgear room) of the reactor building occurred. The CO-2 discharge has been stopped, area ventilation is in progress, and all personnel were evacuated and accounted for. The Nine Mile Point 2 Fire Department was activated to help with this problem and is still in the area until the area is ventilated. The NRC Resident Inspector was notified along with the State and local Government and other agencies.
* * * UPDATE ON 12/21/00 @ 1646 BY LANGE TO GOULD * * *
The NOUE was terminated at 1639 following thorough air sampling of the affected areas to check the oxygen levels. The oxygen levels checked good and the NOUE was terminated.
The NRC Resident Inspector was notified along with the State, local and other Government agencies.
The HOO notified FEMA(Cegielski), EO(Marsh), RDO(Dimitriadis), IRO(Congel)