Event Number: 37299
Facility: HATCH
Region: 2     State: GA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: PAUL UNDERWOOD
HQ OPS Officer: BOB STRANSKY
Notification Date: 09/08/2000
Notification Time: 15:39 [ET]
Event Date: 09/08/2000
Event Time: 13:30 [EDT]
Last Update Date: 09/08/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
MARK LESSER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE COOLANT INJECTION (HPCI) SYSTEM DECLARED INOPERABLE

"At 1330 on 09/08/00, HPCI Flow Controller, 1E41-R612, was observed to be exhibiting erratic indication of flow. Flow indication was oscillating from 0 to >500 gpm with HPCI in its standby condition. Investigation is continuing."

The NRC resident inspector will be informed of this event by the licensee.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Fuel Cycle Facility
Event Number: 37300
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: JEFF CASTLE
HQ OPS Officer: STEVE SANDIN
Notification Date: 09/09/2000
Notification Time: 10:21 [ET]
Event Date: 09/08/2000
Event Time: 20:00 [EDT]
Last Update Date: 09/21/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
GARY SHEAR (R3)
Event Text
24-HOUR NRC BULLETIN 91-01 REPORT INVOLVING SAFETY SYSTEM ACTUATION

"On 9/8/2000 at 2000 hours a safety system actuation occurred in the X344 building. Autoclave #4 was in Mode II 'Heating' when the High Condensate Level Shutoff safety system actuated. Per TSR 2.1.3.7, the autoclave was placed in Mode VII 'Shutdown', a mode in which the High Condensate level Shutoff system is not required, and declared inoperable. This is being reported as a valid safety system actuation. An engineering evaluation has been initiated to review the system conditions that surrounded the actuation of the safety system."

Operations notified both the NRC resident inspector and DOE site representative.

* * * RETRACTED AT 2323 EDT ON 9/21/00 BY ERIC SPAETH TO FANGIE JONES * * *

"RETRACTION: On 09/21/00, the Plant Shift Superintendent retracted the above Event. At the time of the High Condensate Level Shutoff (HCLS) system actuation, the autoclave was being cycled on and off in accordance with the applicable procedure for heating a Russian cylinder. Follow up investigation by engineering and operations has determined the HCLS actuation occurred while AC #4 was in Mode VII 'Shutdown'.

"Discussions with building supervision and the operator who witnessed the HCLS actuation revealed the AC #4 had been shutdown as part of the on/off heating cycle before the actuation occurred. Based on the configuration of AC #4 at the time, the AC would have been in Mode VII 'Shutdown'.

"Since the HCLS system is not required to be operable in Mode VII 'Shutdown', the HCLS system actuation was invalid, and is not reportable in accordance with 10CFR76.120(c)(2). Accordingly, this event is being retracted."

The plant has informed the NRC Resident Inspector. The R3DO (Bruce Burgess) and NMSS EO (John Greeves) has been notified.