Event Notification Report for July 08, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
07/07/2000 - 07/08/2000

EVENT NUMBERS
371523715337154

!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 37152
Facility: LIMERICK
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: GREG SOSSON
HQ OPS Officer: DOUG WEAVER
Notification Date: 07/08/2000
Notification Time: 08:33 [ET]
Event Date: 07/08/2000
Event Time: 04:40 [EDT]
Last Update Date: 07/24/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(A) - UNANALYZED COND OP
Person (Organization):
STEVEN DENNIS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 52 Power Operation
Event Text
UNANALYZED CONDITION

At 04:40 the Unit 2 #4 Main Turbine control valve closed. No testing or maintenance was in progress at the time of the valve closure. Plant Operating procedures specify that the MCPR thermal limit is not analyzed for this condition. The appropriate technical specification action is being entered to reduce power to below 25% power within 6 hours. Reactor power is currently 52% and being reduced.

At 07:47 it was determined that an unanalyzed condition exists on Unit 2 that has the potential to compromise plant safety based on the above condition.

The cause of the control valve failure is not determined at this time. At the time of the control valve closure, reactor power and pressure remained stable with one main turbine bypass valve opening approximately 40%. Power was immediately reduced to 95% in accordance with plant procedures. The bypass valve closed.

The licensee notified the NRC resident inspector.

* * * RETRACTED AT 1341 EDT ON 7/24/00 BY STAN GAMBLE TO FANGIE JONES * * *

"This is a retraction of a notification made on 07/08/00 at 08:33 hours, (event #37152). This event was reported as an unanalyzed condition under requirement 10CFR50.72(b)(1)(ii)(A).

"Unit 2 Main Turbine control valve (TCV) failed closed at 100% power. The Technical Specification MCPR thermal limit is not analyzed for extended operation with one TCV in the closed position. Power was reduced to less than 25% within the TS AOT.

"The basis for this retraction is that the effect of the closed TCV has been evaluated by PECO Energy engineering with the following results. The TCV slow closure resulted in a mild pressure transient that did not challenge the MCPR Safety Limit. This phase was bounded by the limiting MCPR event of load reject without bypass.

"The load drop to 25% power was uncomplicated and completed within four (4) hours and twenty (20) minutes. The leading MFLCPR value for this period was 0.961. This complied with the MCPR TS AOT of six (6) hours. This period was of short duration and bounded by the existing Design Bases Accidents.

"The MCPR TS LCO is not applicable to operation at less than 25% power. This period of operation is also considered analyzed.

"Since all phases of the transient and reduced power operation are explicitly analyzed or bounded by existing analysis, this event is considered analyzed. In addition, this event did not significantly compromise plant safety.
An unanalyzed condition that significantly compromises plant safety did not occur. Therefore, this event is not reportable per the guidance of NUREG-1022, Rev 1."

The licensee notified the NRC Resident Inspector. The NRC Operations Officer notified the R1DO (Mohamed Shanbaky)


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 37153
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: JOHN CLAIRE
HQ OPS Officer: BOB STRANSKY
Notification Date: 07/08/2000
Notification Time: 22:19 [ET]
Event Date: 07/08/2000
Event Time: 21:07 [EDT]
Last Update Date: 07/17/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
STEVEN DENNIS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
UNIT OUTSIDE OF DESIGN BASIS FOLLOWING CIRCULATING WATER SYSTEM BACKFLUSHING

The licensee reported that the service water system inlet temperature exceeded the design basis temperature of 75° F for approximately 9 minutes following the completion of a condenser backwashing operation. Actual system temperatures increased from an initial temperature of 66° F to a high of 90.6° F before returning to normal.

The licensee stated that a new procedure for cleaning the circulating water system was being used; instead of elevating and holding system temperature ("mussel cooking"), a high flow rate "velocity flush" was performed. The flushing was performed for approximately four minutes, during which time service water inlet temperatures remained normal. However, after the flushing was completed, service water system inlet temperatures, as measured at various system headers, increased unexpectedly. The licensee has cancelled additional flushing operations that had been planned for the weekend.

The NRC resident inspector has been informed of this event by the licensee.


* * * UPDATE ON 7/17/00 @ 1049 BY NELSON TO GOULD * * * RETRACTION

Subsequent review and evaluation determined that the plant did operate within the confines of its design basis. Therefore, this event was not reportable pursuant to 10 CFR 50.72(b)(1)(ii)(B). This report is therefore withdrawn.

Specifically, as stated in the Basis for the Ultimate Heat Sink Technical Specification (TS 3.7.11), the limitation on the ultimate heat sink temperature ensures that sufficient cooling is available to either:

1.provide normal cooldown of the facility, or
2. to mitigate the effects of accident conditions within acceptable limits.

This limitation is based on a 30 day cooling water supply to safety related equipment without exceeding their design basis temperature. This basis constitutes the design basis for the ultimate heat sink temperature limitation.

The temperature excursion that occurred was approximately 8 minutes in duration. This period of time constitutes less than 2/1000 of 1 percent of the aggregate time and is therefore insignificant relative to maintaining a 30 day cooling water supply. Additionally, the indicated temperature at the Vital switchgear cooling heat exchanger (X-183), while peaking at 90.6 °F, was not indicative of the bulk (i.e. Long Island Sound) temperature of the ultimate heat sink but rather was a localized effect resulting from the planned backwashing
evolution that was the direct cause of the increased temperature indication.

The magnitude and duration of the temperature excursion was such that it would not have inhibited the units ability to perform a normal cooldown of the facility if it had been required. In addition, since the ultimate heat sink temperature was restored to less than 75 °F within 8 minutes, the ability to provide a 30 day cooling water supply to safety related equipment without exceeding their design basis temperature supply was not impacted. Therefore, the power plant was not in a condition during operation that resulted in the nuclear power plant being
outside of the design basis.

The NRC Resident Inspector was notified. The Reg 1 RDO(Cranston) was informed.


Other Nuclear Material
Event Number: 37154
Rep Org: U.S. ARMY
Licensee: U.S. ARMY
Region: 3
City: ROCK ISLAND   State: IL
County:
License #: 12-00722-06
Agreement: Y
Docket:
NRC Notified By: JEFF HAVENNER
HQ OPS Officer: DOUG WEAVER
Notification Date: 07/10/2000
Notification Time: 09:26 [ET]
Event Date: 07/08/2000
Event Time: 12:17 [CDT]
Last Update Date: 07/10/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(ii) - LOST/STOLEN LNM>10X
Person (Organization):
MICHAEL JORDAN (R3)
DON COOL (NMSS)
Event Text
STOLEN CHEMICAL AGENT DETECTOR

AN M43A1 CHEMICAL AGENT DETECTOR WAS STOLEN FROM THE TWIN BRIDGES TRAINING AREA IN THE REPUBLIC OF KOREA DURING A RECENT EXERCISE. THE DETECTOR CONTAINS 250 µCi of Am-241. THE ARMY HAS NOTIFIED THE REPUBLIC OF KOREA.