Event Notification Report for July 03, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
07/02/2000 - 07/03/2000

EVENT NUMBERS
37140

Power Reactor
Event Number: 37140
Facility: FITZPATRICK
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: BERNARD HORNING
HQ OPS Officer: FANGIE JONES
Notification Date: 07/03/2000
Notification Time: 11:10 [ET]
Event Date: 07/03/2000
Event Time: 10:20 [EDT]
Last Update Date: 07/03/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
STEVEN DENNIS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF THE 'A' REACTOR PROTECTION SYSTEM BUS CAUSING MULTIPLE AUTOMATIC ACTIONS

The unit experienced a loss of 'A' reactor protection system (RPS) bus. RPS motor generator output breakers opened and deenergized the bus, this caused the 'A' standby gas treatment to automatically start. Also the 'A' hydrogen/oxygen monitor isolation valves closed, reactor building ventilation isolated, and the reactor water cleanup system tripped due to isolation valve closure.

This trip appears to be "identical" to a trip reported on 6/26/00, event #37119.

The licensee has energized the 'A' RPS bus and returned all systems to normal operation with the exception of reactor water cleanup, which is being restored.

The licensee has notified the NRC Resident Inspector.