Skip to main content

Event Notification Report for June 23, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/22/2000 - 06/23/2000

EVENT NUMBERS
371093711037111

General Information or Other
Event Number: 37109
Rep Org: US AIR FORCE
Licensee: US AIR FORCE
Region: 4
City: BARKSDALE AFB   State: LA
County:
License #: 422353901-AF
Agreement: Y
Docket:
NRC Notified By: WROBEL
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/23/2000
Notification Time: 12:54 [ET]
Event Date: 06/23/2000
Event Time: 11:00 [CDT]
Last Update Date: 06/23/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
JOE TAPIA (R4)
KEVIN RAMSEY (NMSS)
Event Text
THE US AIR FORCE REPORTED 18 LOST/STOLEN LENSATIC COMPASSES.


In March, 2000 the Air Force recalled all lensatic compasses NSN 6605-00-151-5337 and Barksdale AF Base, La. inadvertently sent 17 of these compasses to the Defense Reutilization Management Organization (DRMO) in Texarkanna,Tx. DRMO has no record of receiving these 17 compasses from Barksdale AFB. Since this time, Barksdale base supply had collected 3 more of these compasses and as of 6/3/00 one has been identified as being missing. Each of these 18 missing compasses contain 120 millicuries or less of tritium. Barksdale base supply is conducting an intense search for these compasses.


Power Reactor
Event Number: 37110
Facility: DUANE ARNOLD
Region: 3     State: IA
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: HAUNER
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/23/2000
Notification Time: 19:33 [ET]
Event Date: 06/23/2000
Event Time: 16:17 [CDT]
Last Update Date: 06/23/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
ROGER LANKSBURY (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Shutdown
Event Text
REACTOR SCRAM FROM 100% POWER DUE TO TURBINE TRIP.

During normal reactor operation at 100% power a turbine trip occurred causing a reactor SCRAM. A reactor recirc pump trip initiated and functioned normally. Four SRVs and both bypass valves opened to initially control reactor pressure. No. 1 bypass valve remained open for subsequent pressure control. The reactor vessel level transient (164 to 198 inches) resulted in a low level (170 inches) Group 2, 3, and 4 isolations.

Subsequent to the reactor SCRAM, a Reactor Feed Pump and HPCI turbine high level trip occurred (HPCI was not running at this time) at 211 inches. Operator took action to restore reactor vessel level and restart the 'B' reactor feed pump.

The exact cause of the turbine trip is unknown at this time. An intermittent 125 VDC Div 1 ground occurred following the SCRAM which is also under investigation.

A reactor recirc pump could not be restarted due to a high temperature difference and a normal cooldown was initiated to mitigate concerns of thermal stratification.

All rods fully inserted and the condenser is being used as the heat sink.

The NRC Resident Inspector was notified.


Power Reactor
Event Number: 37111
Facility: OYSTER CREEK
Region: 1     State: NJ
Unit: [1] [] []
RX Type: [1] GE-2
NRC Notified By: BROWN
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/23/2000
Notification Time: 20:54 [ET]
Event Date: 06/23/2000
Event Time: 01:00 [EDT]
Last Update Date: 06/23/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
CURTIS COWGILL (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
THE LICENSEE NOTIFIED THE NATIONAL MARINE FISHERY SERVICE OF A TRAPPED LOGGERHEAD SEA TURTLE.

THE LICENSEE FOUND A LIVE LOGGERHEAD SEA TURTLE AT THE DILUTION STRUCTURE INTAKE TRASH BARS, REMOVED AND TRANSPORTED IT TO THE MARINE MAMMAL STRANDING CENTER.

THE NRC RESIDENT INSPECTOR WAS NOTIFIED.