Event Notification Report for June 17, 2000
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
06/16/2000 - 06/17/2000
EVENT NUMBERS
37093
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 37093
Facility: MONTICELLO
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: KEVIN PEDERSON
HQ OPS Officer: STEVE SANDIN
Region: 3 State: MN
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: KEVIN PEDERSON
HQ OPS Officer: STEVE SANDIN
Notification Date: 06/17/2000
Notification Time: 13:00 [ET]
Event Date: 06/17/2000
Event Time: 11:15 [CDT]
Last Update Date: 07/14/2000
Notification Time: 13:00 [ET]
Event Date: 06/17/2000
Event Time: 11:15 [CDT]
Last Update Date: 07/14/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(i)(A) - PLANT S/D REQD BY TS
10 CFR Section:
50.72(b)(1)(i)(A) - PLANT S/D REQD BY TS
Person (Organization):
DAVID HILLS (R3)
DAVID HILLS (R3)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
UNIT ENTERED A TECH SPEC REQUIRED SHUTDOWN AFTER DECLARING BOTH CONTAINMENT SPRAY TRAINS INOPERABLE
"BOTH LOOPS OF RHRSW (RESIDUAL HEAT REMOVAL SERVICE WATER) WERE DECLARED INOPERABLE DURING THE FILL PROCESS FOLLOWING MAINTENANCE ON '14' RHRSW PUMP MOTOR. PER TECH 3.5.C.3, BOTH LOOPS OF CONTAINMENT SPRAY/COOLING WERE DECLARED INOPERABLE REQUIRING A REACTOR SHUTDOWN AND TEMPERATURE LESS THAN 212°F IN 24 HOURS. INITIAL INVESTIGATION ASSUMES THE DISCHARGE CHECK VALVE ON THE '14 RHRSW PUMP DID NOT SEAT. AT THIS TIME THE 'A' LOOP OF RHRSW HAS BEEN RESTORED AND THE PLANT IS IN A 7 DAY LCO."
THE UNIT ENTERED AND EXITED THE SHUTDOWN ACTION STATEMENT AT 1115CDT AND 1130CDT, RESPECTIVELY WITH NO POWER REDUCTION OCCURRING.
THE LICENSEE WILL INFORM STATE/LOCAL AGENCIES AND THE NRC RESIDENT INSPECTOR.
* * * RETRACTED ON 7/14/00 AT 1640 EDT BY JIM McCAY TO FANGIE JONES * * *
"This notification retracts a notification made 6/17/00 for both loops of RHRSW being declared inoperable due to low system standby pressure. The original notification should have been made under 10CFR50.72 (b)(2)(iii) , as a condition that alone could have prevented fulfillment of a safety function, rather than under 10CFR50.72 (b)(1)(a) as initiation of a plant shutdown required by Tech Spec. No plant shutdown was initiated. The low RHRSW standby pressure condition is a concern with respect to voids forming in the piping system with subsequent water hammer during pump start. Review of system response when 'A' loop was returned to service indicated no voiding had occurred and 'A' loop or RHRSW was operabie during the event. Thus, the 'A' loop could have performed the required safety functions of RHRSW and the condition is not reportable."
The licensee notified the NRC Resident Inspector and the state and local authorities. The NRC Operations Officer notified the R3DO (Bruce Jorgensen).
"BOTH LOOPS OF RHRSW (RESIDUAL HEAT REMOVAL SERVICE WATER) WERE DECLARED INOPERABLE DURING THE FILL PROCESS FOLLOWING MAINTENANCE ON '14' RHRSW PUMP MOTOR. PER TECH 3.5.C.3, BOTH LOOPS OF CONTAINMENT SPRAY/COOLING WERE DECLARED INOPERABLE REQUIRING A REACTOR SHUTDOWN AND TEMPERATURE LESS THAN 212°F IN 24 HOURS. INITIAL INVESTIGATION ASSUMES THE DISCHARGE CHECK VALVE ON THE '14 RHRSW PUMP DID NOT SEAT. AT THIS TIME THE 'A' LOOP OF RHRSW HAS BEEN RESTORED AND THE PLANT IS IN A 7 DAY LCO."
THE UNIT ENTERED AND EXITED THE SHUTDOWN ACTION STATEMENT AT 1115CDT AND 1130CDT, RESPECTIVELY WITH NO POWER REDUCTION OCCURRING.
THE LICENSEE WILL INFORM STATE/LOCAL AGENCIES AND THE NRC RESIDENT INSPECTOR.
* * * RETRACTED ON 7/14/00 AT 1640 EDT BY JIM McCAY TO FANGIE JONES * * *
"This notification retracts a notification made 6/17/00 for both loops of RHRSW being declared inoperable due to low system standby pressure. The original notification should have been made under 10CFR50.72 (b)(2)(iii) , as a condition that alone could have prevented fulfillment of a safety function, rather than under 10CFR50.72 (b)(1)(a) as initiation of a plant shutdown required by Tech Spec. No plant shutdown was initiated. The low RHRSW standby pressure condition is a concern with respect to voids forming in the piping system with subsequent water hammer during pump start. Review of system response when 'A' loop was returned to service indicated no voiding had occurred and 'A' loop or RHRSW was operabie during the event. Thus, the 'A' loop could have performed the required safety functions of RHRSW and the condition is not reportable."
The licensee notified the NRC Resident Inspector and the state and local authorities. The NRC Operations Officer notified the R3DO (Bruce Jorgensen).