Skip to main content

Event Notification Report for June 15, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/14/2000 - 06/15/2000

EVENT NUMBERS
37090370873708837084

General Information or Other
Event Number: 37090
Rep Org: YALE UNIVERSITY
Licensee: YALE UNIVERSITY
Region: 1
City: NEW HAVEN   State: CT
County:
License #:
Agreement: N
Docket:
NRC Notified By: TAMMY STEMEN
HQ OPS Officer: STEVE SANDIN
Notification Date: 06/16/2000
Notification Time: 16:01 [ET]
Event Date: 06/15/2000
Event Time: 16:58 [EDT]
Last Update Date: 06/16/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MOHAMED SHANBAKY (R1)
SCOTT MOORE (NMSS)
Event Text
POTENTIAL PERSONNEL OVEREXPOSURE

A technician employed by Yale University in the Environmental Services Group expressed a concern regarding ALARA during an inventory of both byproduct and accelerator produced radioactive material. He noticed a vial containing Na-22 (accelerator product) in the millicurie source range sitting on its side in the "cave." The "cave" is a shielded storage location for both waste and byproduct material. The technician's film was sent for an emergency read. The results were received at 1658EDT on 6/15/00 and indicated a whole body exposure of 6930 mRem. A thyroid scan and bioassays were performed with negative results. Contamination surveys were performed, again with negative results. The technician had taken his film badge with him to Texas during the period of time the badge was used (May). The University RSO has submitted the other technicians (between 30-35) film badges for reading as part of the investigation. The University has contacted the state of CT.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 37087
Facility: CLINTON
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: MARSHALL FUNKHOUSER
HQ OPS Officer: STEVE SANDIN
Notification Date: 06/15/2000
Notification Time: 21:54 [ET]
Event Date: 06/15/2000
Event Time: 19:15 [CDT]
Last Update Date: 06/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
DAVID HILLS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE CORE SPRAY (HPCS) DECLARED INOPERABLE DUE TO INCOMPLETE POST MODIFICATION TESTING OF IT'S ASSOCIATED DIESEL GENERATOR

"At 1915 on 6/15/00 a Engineering review of a plant modification to the Division 3 Diesel Generator (DG) determined that the Post Modification Testing did not verify proper operation of the Loss of Off-Site Power (LOOP) circuitry. This modification had only been performed to Division 3 DG and therefore Division 1 and 2 DG's are not affected. Division 3 DG provides power to the High Pressure Core Spray (HPCS) pump. The failure of Division 3 DG to operate during a LOOP would have prevented HPCS from operating. The loss of a single train safety system such as HPCS is reportable under 10CFR50.72(b)(2)(iii)(D)."

The plant modification involved rewiring the electrical circuit to correct for a degraded voltage condition and was completed on 1/24/99. Post modification testing was completed on 1/31/99. HPCS has been declared inoperable but is available, if needed, pending completion of additional testing. The licensee will inform the NRC Resident Inspector.

* * * UPDATE 2115EDT ON 6/27/00 FROM CHEAR TO S. SANDIN * * *

The licensee is retracting this report based on the following:

"Further review of this issue has determined that Division 3 Diesel Generator (DG) output breaker control circuit has been operable since installation of the modification and the plant was never in a condition that alone could have prevented fulfillment of the safety function. Therefore, Clinton Power Station is retracting Event Notification # 37087."

The licensee informed the NRC Resident Inspector. Notified R3DO(Leach).


Power Reactor
Event Number: 37088
Facility: SUMMER
Region: 2     State: SC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: DAN GOLDSTON
HQ OPS Officer: STEVE SANDIN
Notification Date: 06/15/2000
Notification Time: 22:10 [ET]
Event Date: 06/15/2000
Event Time: 21:37 [EDT]
Last Update Date: 06/15/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(i)(A) - PLANT S/D REQD BY TS
Person (Organization):
RUDOLPH BERNHARD (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 99 Power Operation
Event Text
UNIT COMMENCED A CONTROLLED TECH SPEC REQUIRED SHUTDOWN TO MODE 2 FOR REPAIRS

"The 'C' steam generator Feedwater Isolation Valve, XVG1611C, air operator developed an air leak and was declared inoperable 6/13/00 at 1549EDT. Efforts to stop the leak were unsuccessful. At 2137EDT on 6/15/00 a controlled power reduction to mode 2 was started. Current plans are to repair the operator in mode 2 and return to power operation."

The air leak is ongoing with the affected valve in use (open). The licensee anticipates entering mode 2 by 0600EDT on 6/16/00 and has informed the NRC Resident Inspector.


Power Reactor
Event Number: 37084
Facility: BRUNSWICK
Region: 2     State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: JOE COSTA
HQ OPS Officer: FANGIE JONES
Notification Date: 06/15/2000
Notification Time: 07:51 [ET]
Event Date: 06/15/2000
Event Time: 06:57 [EDT]
Last Update Date: 06/15/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - EMERGENCY SIREN INOP 50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
RUDOLPH BERNHARD (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
LOSS OF NINE EMERGENCY OFFSITE SIRENS DUE TO LOSS OF LOCAL POWER

The licensee was notified that at 0657 EDT that nine of the offsite emergency warning sirens were deenergized at 0408 EDT due to local power outage and were inoperable for greater than one hour. Six were restored in 1 hour and 16 minutes and the other three were restored in 2 hours and 16 minutes. All sirens are now operable.

The licensee notified the NRC Resident Inspector and the State authorities.