Event Number: 36971
Facility: HARRIS
Region: 2     State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: CASPER JERNIGAN
HQ OPS Officer: FANGIE JONES
Notification Date: 05/04/2000
Notification Time: 16:36 [ET]
Event Date: 05/04/2000
Event Time: 13:24 [EDT]
Last Update Date: 05/04/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
ROBERT HAAG (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
INADVERTENT SAFETY INJECTION ACTUATION

"Harris Nuclear Plant was in Mode-5 with Reactor Vessel level at -12 inches following Mid-Loop operations. A Safety Injection Signal was actuated when Instrument Bus S-III was de-energized to return it to its normal power supply. Plant procedure MST-I0604 (Time Response Test for Channel 1 Pressurizer Pressure) was in progress. This procedure had channel 1 Pressurizer Pressure in test. When S-III was de-energized, the Low Pressurizer Pressure SI and Low Steam Generator Pressure SI Block signal (P-11) were unblocked due to Pressurizer channel III being de-energized concurrent with Pressurizer channel 1 in test. The plant was in Mode-5 with Pressurizer Pressure and Steam Generator Pressure at approximately 0 psig. Pressurizer Low Pressure SI and Low Steam Generator Pressure SI actuated the SI signal after P-11 was unblocked. Preparations to perform OST 1826 "Safety Injection: ESF Response Time, Train B 18 Month Interval test" were in progress. This test had the BIT injection valves closed with power off, which prevented ECCS discharge to the RCS. Other equipment operated as required in response to the Safety Injection Signal in these plant conditions. This actuation did not have any negative impact on RCS temperature or inventory control. The plant is currently stable in Mode-5."

The licensee notified the NRC Resident Inspector.


Other Nuclear Material
Event Number: 36972
Rep Org: U.S. ARMY
Licensee: U.S. ARMY
Region: 2
City: REDSTONE ARSENAL   State: AL
County:
License #: SNM1998
Agreement: Y
Docket:
NRC Notified By: JERRY GRAY
HQ OPS Officer: FANGIE JONES
Notification Date: 05/04/2000
Notification Time: 16:54 [ET]
Event Date: 05/04/2000
Event Time: 00:00 [CDT]
Last Update Date: 05/04/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
ROBERT HAAG (R2)
JOSEPHINE PICCONE (NMSS)
NIEL DELLA GRECA (R1)
BRUCE BURGESS (R3)
Event Text
SOURCE SET LOST DURING SHIPPING

Operations for US Army Communications Electronics Command at Fort Monmouth, New Jersey shipped, via FedEx, an Amersham large area alpha calibration source to US Army at Redstone Arsenal, Alabama on 3/15/2000. The calibration set (serial # LAAS-003) contains 3 sources (serial #'s ES-927, 928 and 929) with a total of about 18 microcuries of Pu-238. On 4/18/2000, Redstone Arsenal contacted US Army Communications Electronics Command in New Jersey to inquire about a leak test that was due on the calibration source, who in turn informed them that it had been shipped to them in March. A search was conducted at Redstone Arsenal without the calibration source set being found. FedEx was contacted and a search of the sort center in New Jersey, to which the shipment was traced, failed to locate the shipment. The US Army is reporting that the source set is missing, assumed lost or stolen.


Power Reactor
Event Number: 36973
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [] [3] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: RUSSELL LONG
HQ OPS Officer: FANGIE JONES
Notification Date: 05/04/2000
Notification Time: 18:00 [ET]
Event Date: 05/04/2000
Event Time: 14:41 [EDT]
Last Update Date: 05/04/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
NIEL DELLA GRECA (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
ABOUT 25 DEAD FISH DISCOVERED IN DISCHARGE CANAL

"On May 4, 2000, at approximately 1441 hours, plant personnel discovered dead fish in the discharge canal. There were no plant events or occurrences that appear to be causally related. The fish numbered about 25, had an average length of about one foot and consisted of gizzard shad, not an endangered species. The water in the discharge canal is river water used for cooling plant equipment in both Indian Point 2 and 3 during plant operation. The fish could not have traveled through the plant to the discharge canal since the river water intake has screens to prevent this type of fish intrusion.

"This event is reported, within 24 hours, pursuant to Non-radiological Environmental Technical Specification 4.1 as an unusual event, a fish kill. The cause is being evaluated."

The licensee intends to notify the NRC Resident Inspector.


Power Reactor
Event Number: 36974
Facility: LASALLE
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] GE-5,[2] GE-5
NRC Notified By: RICHARD CALVIN
HQ OPS Officer: FANGIE JONES
Notification Date: 05/04/2000
Notification Time: 19:02 [ET]
Event Date: 05/04/2000
Event Time: 13:18 [CDT]
Last Update Date: 05/04/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
BRUCE BURGESS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
REACTOR WATER CLEANUP SYSTEM AUTOMATICALLY ISOLATED

The reactor water cleanup system (RWCU) isolated due to ESF signal "high flow isolation signal". Originally it was determined to be an invalid signal caused by a pressure pulse induced by human error. Additional information indicates that it cannot be proven that the isolation was not caused by system flow, therefore it has been determined that the event is reportable. The system isolated as designed and has been restored.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 36975
Facility: DRESDEN
Region: 3     State: IL
Unit: [] [] [3]
RX Type: [1] GE-1,[2] GE-3,[3] GE-3
NRC Notified By: DAVID SLAGER
HQ OPS Officer: FANGIE JONES
Notification Date: 05/04/2000
Notification Time: 22:09 [ET]
Event Date: 05/04/2000
Event Time: 20:18 [CDT]
Last Update Date: 05/04/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
BRUCE BURGESS (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 M/R Y 44 Power Operation 0 Hot Standby
Event Text
DECREASING CONDENSER VACUUM REQUIRED MANUAL REACTOR SCRAM

"During unit startup from D3F30 forced outage, condenser vacuum was reducing on 2 of 3 condenser hoods and condensate demin inlet temperatures were rising. The abnormal operating procedure for loss of condenser vacuum was entered and actions followed to scram at 135 °F condensate temp. All systems responded as designed with no abnormalities noted. Investigation into cause in progress."

All rods fully inserted following the manual reactor scram. Group 2 and 3 isolations were received as expected on reduced reactor vessel level.

The licensee intends to notify the NRC Resident Inspector.