Skip to main content

Event Notification Report for March 27, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
03/26/2000 - 03/27/2000

EVENT NUMBERS
36842368363683736838

Power Reactor
Event Number: 36842
Facility: SUSQUEHANNA
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: GRANT FERNSLER
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 03/28/2000
Notification Time: 22:33 [ET]
Event Date: 03/27/2000
Event Time: 15:30 [EST]
Last Update Date: 03/28/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
MICHELE EVANS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
- ESF ACTUATION OF REACTOR WATER CLEANUP SYSTEM DURING DRAINING EVOLUTIONS -

During the Unit 1 Refueling and Inspection Outage, the licensee determined that the Reactor Water Cleanup System received an ESF Actuation signal during draining evolutions. The potential for an ESF Actuation is identified in the draining procedure, however after review, the licensee determined that the actuation signal was not part of the planned evolution due to the system not being properly removed from service. An actual isolation did not occur due to the isolation valves being bypassed per the draining procedure.

This event has no effect on Unit 2 which is at 100% power.

The licensee is investigating this event and determining corrective actions.

At 2030 on 03/28/00, while reviewing this event, the licensee determined that this event is reportable to the NRC. This failure requires a four hour ENS notification under 10CFR50.72(b)(2)(ii).

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 36836
Facility: HATCH
Region: 2     State: GA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: URQUHART
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 03/27/2000
Notification Time: 09:17 [ET]
Event Date: 03/27/2000
Event Time: 08:00 [EST]
Last Update Date: 03/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - DEG/UNANALYZED COND
Person (Organization):
THOMAS DECKER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Refueling 0 Refueling
Event Text
FAILURE OF LOCAL LEAK RATE TEST.

DURING LOCAL LEAK RATE TESTING(LLRT) OF THE "2G11-F004", DRYWELL FLOOR DRAIN SUMP PRIMARY CONTAINMENT ISOLATION VALVE, IT WAS DETERMINED THAT THE VALVE LEAKS AT A RATE GREATER THAN 30,000 ACCM(ACTUAL CUBIC CENTIMETERS/MIN) WHICH IS GREATER THAN THE PROCEDURAL LIMITS. THIS IN COMBINATION WITH ITS COMPANION( IN SERIES) ISOLATION VALVE(2G11-F003) WHICH HAD FAILED A PREVIOUS LLRT AND WAS REPAIRED, BUT FAILED ITS RETEST, RESULTED IN THE TECH SPEC LIMIT FOR 0.009L-SUB-A BEING EXCEEDED FOR BYPASS LEAKAGE. THE TEST WAS PERFORMED ON 3/26 AND WAS EVALUATED THIS MORNING.

THE RESIDENT INSPECTOR WAS NOTIFIED.


General Information or Other
Event Number: 36837
Rep Org: FLORIDA BUREAU OF RADIATION CONTROL
Licensee: DUNKELBERGER ENGINEERING & TESTING
Region: 2
City: WEST PALM BEACH   State: FL
County: PALM BEACH
License #: 2462-2 (FL)
Agreement: Y
Docket:
NRC Notified By: CHARLEY E. ADAMS (FL)
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 03/27/2000
Notification Time: 10:00 [ET]
Event Date: 03/27/2000
Event Time: 00:00 [EST]
Last Update Date: 03/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
THOMAS DECKER (R2)
BRIAN SMITH (NMSS)
Event Text
AGREEMENT STATE REPORT INVOLVING RECOVERED TROXLER GAUGE

"Citizen found troxler gauge [containing 8mCi Cs-137 and 40mCi Am-241:Be] along road and took it to the Royal Palm Beach PD. Owner notified this office of missing gauge, was told of it's location [Intersection of 41 & 67 in Royal Palm Beach], and then took possession. There was no damage to the gauge which was in a locked case. Owner said that the operator failed to secure the gauge to the truck when leaving a work site. Florida is investigating the incident [Florida Incident #FL00-054]."

The licensee lost the device on the morning of 3/27/00 when it fell off his truck due to not being properly secured.

Call the Headquarters Operations Center for contact information.


Power Reactor
Event Number: 36838
Facility: SEQUOYAH
Region: 2     State: TN
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: TERRY KNUETTEL
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 03/27/2000
Notification Time: 14:43 [ET]
Event Date: 03/27/2000
Event Time: 10:08 [EST]
Last Update Date: 03/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
26.73 - FITNESS FOR DUTY
Person (Organization):
THOMAS DECKER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
FITNESS FOR DUTY EVENT -

A temporary employee foreman tested positive for illegal drugs during a random drug test. The licensee terminated the employee's plant access authorization. Contact the NRC Operations Officer for additional details. The licensee notified the NRC Resident Inspector.