Event Notification Report for February 27, 2000
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
02/26/2000 - 02/27/2000
EVENT NUMBERS
36733
Power Reactor
Event Number: 36733
Facility: HATCH
Region: 2 State: GA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: TIM BEINKE
HQ OPS Officer: STEVE SANDIN
Region: 2 State: GA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: TIM BEINKE
HQ OPS Officer: STEVE SANDIN
Notification Date: 02/27/2000
Notification Time: 17:02 [ET]
Event Date: 02/27/2000
Event Time: 16:30 [EST]
Last Update Date: 02/27/2000
Notification Time: 17:02 [ET]
Event Date: 02/27/2000
Event Time: 16:30 [EST]
Last Update Date: 02/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
CHARLES OGLE (R2)
CHARLES OGLE (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
HIGH PRESSURE CORE INJECTION (HPCI) DECLARED INOPERABLE DUE TO WATER INTRUSION INTO THE HPCI PUMP OIL RESERVOIR
During a routine surveillance for operability, the HPCI bracket drain clogged causing seal leakoff to spill into the HPCI oil reservoir. The bracket drain line collects seal leakoff and directs the flow to the floor drain system. HPCI was declared inoperable per Tech Spec 3.5.1 placing Unit 2 in a 14-day LCO. The licensee estimates that the oil will be changed and HPCI restored by approximately 2400 hours on 2/27/00.
The licensee will inform the NRC resident inspector.
During a routine surveillance for operability, the HPCI bracket drain clogged causing seal leakoff to spill into the HPCI oil reservoir. The bracket drain line collects seal leakoff and directs the flow to the floor drain system. HPCI was declared inoperable per Tech Spec 3.5.1 placing Unit 2 in a 14-day LCO. The licensee estimates that the oil will be changed and HPCI restored by approximately 2400 hours on 2/27/00.
The licensee will inform the NRC resident inspector.