Event Notification Report for February 13, 2000
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
02/12/2000 - 02/13/2000
Power Reactor
Event Number: 36686
Facility: CATAWBA
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: J. K. McCONNELL
HQ OPS Officer: LEIGH TROCINE
Region: 2 State: SC
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: J. K. McCONNELL
HQ OPS Officer: LEIGH TROCINE
Notification Date: 02/13/2000
Notification Time: 19:56 [ET]
Event Date: 02/13/2000
Event Time: 18:32 [EST]
Last Update Date: 02/13/2000
Notification Time: 19:56 [ET]
Event Date: 02/13/2000
Event Time: 18:32 [EST]
Last Update Date: 02/13/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
MARK LESSER (R2)
MARK LESSER (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | A/R | Y | 100 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP DUE TO A TURBINE TRIP FOR UNKNOWN REASONS
The following text is a portion of a facsimile received from the licensee:
"Unit 1 reactor trip occurred at 1832 hours on 02/13/2000. Control room annunciators indicate that the cause of the reactor trip was a turbine trip. At this time, the cause of the turbine trip is unknown. All systems and plant responses to the reactor trip were normal."
The licensee stated that all control rods fully inserted and that all support systems functioned correctly. None of the primary or secondary system safety relief valves lifted. There were no emergency core cooling system actuations, and none were required. The following three engineered safety feature actuations occurred: turbine trip (for unknown reasons), feedwater isolation, and auxiliary feedwater automatic start. Feedwater isolated and auxiliary feedwater automatically started as designed.
The cause of the turbine trip is unknown but is currently believed to be electrical in nature. There were no related maintenance or surveillance activities ongoing at the time of the event.
The unit is currently stable in Mode 3 (Hot Standby). Normal charging and letdown, pressurizer heaters and sprays, and the reactor coolant pumps are being utilized at this time for primary system level, pressure, and transport control. Auxiliary feedwater is supplying water to the steam generators, and secondary steam is being dumped to the condenser. The electrical grid is stable.
The licensee notified the NRC resident inspector.
The following text is a portion of a facsimile received from the licensee:
"Unit 1 reactor trip occurred at 1832 hours on 02/13/2000. Control room annunciators indicate that the cause of the reactor trip was a turbine trip. At this time, the cause of the turbine trip is unknown. All systems and plant responses to the reactor trip were normal."
The licensee stated that all control rods fully inserted and that all support systems functioned correctly. None of the primary or secondary system safety relief valves lifted. There were no emergency core cooling system actuations, and none were required. The following three engineered safety feature actuations occurred: turbine trip (for unknown reasons), feedwater isolation, and auxiliary feedwater automatic start. Feedwater isolated and auxiliary feedwater automatically started as designed.
The cause of the turbine trip is unknown but is currently believed to be electrical in nature. There were no related maintenance or surveillance activities ongoing at the time of the event.
The unit is currently stable in Mode 3 (Hot Standby). Normal charging and letdown, pressurizer heaters and sprays, and the reactor coolant pumps are being utilized at this time for primary system level, pressure, and transport control. Auxiliary feedwater is supplying water to the steam generators, and secondary steam is being dumped to the condenser. The electrical grid is stable.
The licensee notified the NRC resident inspector.
Power Reactor
Event Number: 36685
Facility: CALLAWAY
Region: 4 State: MO
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: ROBERT BARTON
HQ OPS Officer: STEVE SANDIN
Region: 4 State: MO
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: ROBERT BARTON
HQ OPS Officer: STEVE SANDIN
Notification Date: 02/13/2000
Notification Time: 11:11 [ET]
Event Date: 02/13/2000
Event Time: 07:34 [CST]
Last Update Date: 02/13/2000
Notification Time: 11:11 [ET]
Event Date: 02/13/2000
Event Time: 07:34 [CST]
Last Update Date: 02/13/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
LINDA HOWELL (R4)
LINDA HOWELL (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | A/R | Y | 100 | Power Operation | 0 | Hot Standby |
AUTOMATIC REACTOR TRIP ON LOSS OF REACTOR COOLANT SYSTEM (RCS) FLOW
THE UNIT EXPERIENCED AN AUTOMATIC REACTOR TRIP-TURBINE TRIP FROM 100% POWER DUE TO THE LOSS OF RCS FLOW CAUSED BY THE TRIP OF THE REACTOR COOLANT PUMPS (INITIALLY "B" RCP FOLLOWED BY THE "A", "C" AND "D"). FLUCTUATING GRID VOLTAGE DUE TO AN ELECTRICAL PROBLEM IN SOUTHEAST MISSOURI CAUSED THE LOSS OF THE RCPs AND THE OPERATING CIRCULATING WATER (CW) PUMPS. DURING THE PERIOD TIME BEFORE THE RCPs WERE RESTARTED, RCS PRESSURE INCREASED CAUSING ONE (1) PRESSURIZER PORV TO LIFT AND RESEAT (SETPOINT 2335 PSIG - PRIMARY SAFETY SETPOINT IS 2485 PSIG). A SLIGHT INCREASE IN THE PRESSURIZER RELIEF TANK PRESSURE WAS OBSERVED. A FEEDWATER ISOLATION SIGNAL OCCURRED WITH ALL SYSTEMS FUNCTIONING AS EXPECTED INCLUDING AUTOSTART OF ALL AUXILIARY FEEDWATER PUMPS (BOTH MOTOR-DRIVEN AND THE TURBINE-DRIVEN PUMPS). CONDENSER VACUUM WAS LOST AS A RESULT OF THE CW PUMP TRIPS. HOWEVER, TWO (2) CW PUMPS WERE RESTARTED AND THE MAIN CONDENSER PLACED BACK IN SERVICE AS THE HEAT SINK. THE LICENSEE ESTIMATES THAT THE STEAM GENERATOR ATMOSPHERIC DUMPS WERE USED FOR NO MORE THAN 20 MINUTES DURING THE PERIOD OF TIME WHEN THE MAIN CONDENSER WAS NOT AVAILABLE. THERE IS NO INDICATION OF ANY PRIMARY-SECONDARY LEAKAGE PRIOR TO THIS EVENT. THE PLANT IS CURRENTLY STABLE WITH OPERATORS RESTORING MAIN FEEDWATER. BOTH EMERGENCY DIESELS ARE IN STANDBY AND AVAILABLE, IF NEEDED. THE UNIT WILL REMAIN IN MODE 3 PENDING THE OUTCOME OF THE INVESTIGATION INTO THE GRID ELECTRICAL TRANSIENT.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.
THE UNIT EXPERIENCED AN AUTOMATIC REACTOR TRIP-TURBINE TRIP FROM 100% POWER DUE TO THE LOSS OF RCS FLOW CAUSED BY THE TRIP OF THE REACTOR COOLANT PUMPS (INITIALLY "B" RCP FOLLOWED BY THE "A", "C" AND "D"). FLUCTUATING GRID VOLTAGE DUE TO AN ELECTRICAL PROBLEM IN SOUTHEAST MISSOURI CAUSED THE LOSS OF THE RCPs AND THE OPERATING CIRCULATING WATER (CW) PUMPS. DURING THE PERIOD TIME BEFORE THE RCPs WERE RESTARTED, RCS PRESSURE INCREASED CAUSING ONE (1) PRESSURIZER PORV TO LIFT AND RESEAT (SETPOINT 2335 PSIG - PRIMARY SAFETY SETPOINT IS 2485 PSIG). A SLIGHT INCREASE IN THE PRESSURIZER RELIEF TANK PRESSURE WAS OBSERVED. A FEEDWATER ISOLATION SIGNAL OCCURRED WITH ALL SYSTEMS FUNCTIONING AS EXPECTED INCLUDING AUTOSTART OF ALL AUXILIARY FEEDWATER PUMPS (BOTH MOTOR-DRIVEN AND THE TURBINE-DRIVEN PUMPS). CONDENSER VACUUM WAS LOST AS A RESULT OF THE CW PUMP TRIPS. HOWEVER, TWO (2) CW PUMPS WERE RESTARTED AND THE MAIN CONDENSER PLACED BACK IN SERVICE AS THE HEAT SINK. THE LICENSEE ESTIMATES THAT THE STEAM GENERATOR ATMOSPHERIC DUMPS WERE USED FOR NO MORE THAN 20 MINUTES DURING THE PERIOD OF TIME WHEN THE MAIN CONDENSER WAS NOT AVAILABLE. THERE IS NO INDICATION OF ANY PRIMARY-SECONDARY LEAKAGE PRIOR TO THIS EVENT. THE PLANT IS CURRENTLY STABLE WITH OPERATORS RESTORING MAIN FEEDWATER. BOTH EMERGENCY DIESELS ARE IN STANDBY AND AVAILABLE, IF NEEDED. THE UNIT WILL REMAIN IN MODE 3 PENDING THE OUTCOME OF THE INVESTIGATION INTO THE GRID ELECTRICAL TRANSIENT.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.