Power Reactor
Event Number: 36629
Facility: CRYSTAL RIVER
Region: 2     State: FL
Unit: [3] [] []
RX Type: [3] B&W-L-LP
NRC Notified By: BANDHAVER
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 01/27/2000
Notification Time: 11:35 [ET]
Event Date: 01/27/2000
Event Time: 09:00 [EST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
CAUDLE JULIAN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION TO FLORIDA FISH AND WILDLIFE CONSERVATION COMMISSION

A GREEN SEA TURTLE(AN ENDANGERED SPECIES) WAS FOUND IN THE INTAKE. THE TURTLE WILL BE HELD FOR A DAY TO ENSURE ITS HEALTH AND THEN RELEASED IN ACCORDANCE WITH THE FISH AND WILDLIFE CONSERVATION COMMISSION DIRECTIONS.

THE NRC RESIDENT INSPECTOR WILL BE NOTIFIED.


Power Reactor
Event Number: 36632
Facility: COOPER
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: FRED SCHIZAS
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 15:06 [ET]
Event Date: 01/27/2000
Event Time: 11:22 [CST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
GAIL GOOD (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
REACTOR WATER CLEANUP ISOLATION WHILE PLACING SYSTEM IN SERVICE

"During initial repressurization of the reactor water cleanup system (RWCU) after the maintenance outage, the control room received channel 'A' and 'B' RWCU high flow alarm (<=191% of rated flow) and subsequent Group 3 isolation (closure of RWCU-MOV-M015 and RWCU-MOV-M018 inboard / outboard primary containment isolation valves). This actuation occurred while the operator was throttling open RWCU-M018.

The Group 3 was verified per G.O.P. 2.1.22 (Recovery From Group Isolations) and following recovery, system flow was restored."

The NRC resident inspector has been informed of this event by the licensee.


Power Reactor
Event Number: 36633
Facility: MILLSTONE
Region: 1     State: CT
Unit: [] [2] []
RX Type: [1] GE-3,[2] CE,[3] W-4-LP
NRC Notified By: STEVE BAKER
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 15:10 [ET]
Event Date: 01/27/2000
Event Time: 14:57 [EST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
JOHN ROGGE (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 M/R Y 100 Power Operation 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO SECONDARY SYSTEM TRANSIENT

Operators manually tripped the unit from 100% power due to decreasing steam generator water levels caused by a decrease in feedwater flow. Feedwater flow decreased due to a transient in a feedwater heater string. All control rods inserted following the trip. Operators also manually initiated the auxiliary feedwater system to restore steam generator water levels (a confirmatory automatic initiation signal was received). The unit is currently stable in Hot Standby. All systems functioned as expected.

The NRC resident inspector has been informed of this event by the licensee.


Power Reactor
Event Number: 36634
Facility: SURRY
Region: 2     State: VA
Unit: [] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: DARLENE BROCK
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 15:38 [ET]
Event Date: 01/27/2000
Event Time: 12:01 [EST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(C) - POT UNCNTRL RAD REL
Person (Organization):
CAUDLE JULIAN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
EXCESSIVE LEAKAGE THROUGH CONTAINMENT ISOLATION VALVE

"On 1/27/00 at 1201 hours, as-found 10CFR50 Appendix J Type C leakage testing of the outside containment trip valve 2-DA-TV-200B was determined to be greater than 0.6 La. Leakage was determined to be approximately 182 scfh versus total minimum pathway leakage acceptance criteria of 180 scfh.

"On 1/25/00 the inside containment trip valve 2-DA-TV-200A for the same penetration was replaced due to an unsatisfactory 1ST stroke time. Removal and installation of the valve was less than one hour in duration. Following replacement of the valve, Type C leakage was determined to be satisfactory for 2-DA-TV-200A, however, excessive leakage was suspected for the outside trip valve 2-DA-TV-200B.

"By testing conducted on 1/27/00, it was confirmed that during the timeframe of 2-DA-TV-200A replacement, a condition which alone could have prevented the fulfillment of the safety function needed to control the release of radioactive material existed.

"Currently containment integrity is being maintained by closure and deactivation of 2-DA-TV-200A in accordance with the station Technical Specification. Following replacement of 2-DA-TV-200A on 1/25/00, Type C testing was performed with satisfactory results (less than 1 scfh). Currently total minimum pathway leakage is approximately 3 scfh.

This report is being made pursuant 10CFR50.72(b)(2)(iii)."

The licensee has informed the NRC resident inspector of this event.


Other Nuclear Material
Event Number: 36635
Rep Org: USAF RADIOISOTOPE COMMITTEE
Licensee: USAF RADIOISOTOPE COMMITTEE
Region: 4
City: KEESLER AFB   State: LA
County:
License #: 42-23539-AF
Agreement: Y
Docket: 03028641
NRC Notified By: MAJ. HICKS
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 16:51 [ET]
Event Date: 01/27/2000
Event Time: 15:00 [CST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
20.2201(a)(1)(i) - LOST/STOLEN LNM>1000X
Person (Organization):
GAIL GOOD (R4)
LARRY CAMPER (NMSS)
Event Text
MISSING CALIBRATION SOURCE

On 1/26/00, the Keesler AFB Radiation Safety Officer (RSO) was unable to locate a 1.37 µCi Pu-239 calibration source during a routine inventory of Wolfe Hall. During the subsequent investigation, the Wolfe Hall RSO reported that the source was to have been transferred to Kelly AFB in Texas, but it had inadvertently been shipped to McLellan AFB in California. However, the McLellan AFB transportation office has no record of receiving the source. The Keesler AFB RSO will continue to attempt to locate the source.


Power Reactor
Event Number: 36636
Facility: COMANCHE PEAK
Region: 4     State: TX
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: PAUL COX
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 17:12 [ET]
Event Date: 01/27/2000
Event Time: 12:50 [CST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
GAIL GOOD (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
OFFSITE NOTIFICATION DUE TO OIL SHEEN

The licensee notified the Texas Natural Resource Conservation Commission and the US DOT National Response Center regarding the appearance of an oil sheen near the circulating water discharge. The licensee believes that the oil is residue from recent paving activities that has been washed out due to heavy rains. The licensee has deployed absorbent materials to control the spill. The NRC resident inspector has been informed of this event by the licensee.


Power Reactor
Event Number: 36637
Facility: SAN ONOFRE
Region: 4     State: CA
Unit: [] [2] [3]
RX Type: [1] W-3-LP,[2] CE,[3] CE
NRC Notified By: A. BOLYEN
HQ OPS Officer: BOB STRANSKY
Notification Date: 01/27/2000
Notification Time: 19:13 [ET]
Event Date: 01/27/2000
Event Time: 15:30 [PST]
Last Update Date: 01/27/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
GAIL GOOD (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
3 N Y 100 Power Operation 100 Power Operation
Event Text
UNITS OUTSIDE OF DESIGN BASIS DUE TO WORDING OF UFSAR

"This notification is for San Onofre Units 2 and 3 and is being made in accordance with 10CFR50.72(b)(1)(ii)(B).

"Southern California Edison was performing a review of plant drawings and noticed a potential discrepancy between some circuit designs and the specific wording used in the Updated Final Safety Analysis Report (UFSAR) to describe the design for those circuits. Further investigation of the affected components revealed that certain functions appear to not fully meet the separation criteria of Regulatory Guide 1.75, 'Physical Independence of Electrical Systems.' These circuits include relays for portions of some Engineered Safety Features (e.g., boric acid makeup pumps and input voltage to one of the four loss-of-voltage-signal circuits). The UFSAR for Units 2 and 3 indicates these systems comply with IEEE-279, 1971, 'Criteria for Protection Systems for Nuclear Power Generation Stations' which is referenced by Regulatory Guide 1.75. Consequently, at 1530 PDT, SCE concluded this condition was reportable in accordance with 10CFR50.72(b)(1)(ii)(B) as a condition 'outside the design basis of the plant.'

"SCE has confirmed that the affected components remain capable of performing their intended safety functions and, therefore, concludes there is no safety significance to this occurrence.

"At the time of this report. Unit 1 remains permanently shutdown, and Units 2 and 3 are operating at about 100% power. SCE will notify the NRC resident inspectors of this condition and provide them with a copy of this report."