Event Notification Report for January 03, 2000

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/02/2000 - 01/03/2000

EVENT NUMBERS
365563655736558

Power Reactor
Event Number: 36556
Facility: POINT BEACH
Region: 3     State: WI
Unit: [] [2] []
RX Type: [1] W-2-LP,[2] W-2-LP
NRC Notified By: JOHN SELL
HQ OPS Officer: JOHN MacKINNON
Notification Date: 01/03/2000
Notification Time: 12:33 [ET]
Event Date: 01/03/2000
Event Time: 11:20 [CST]
Last Update Date: 01/03/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
JOHN MADERA (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
"C" CHARGING PUMP APPENDIX "R" CONCERN

During the Appendix "R" rebaselining project it was discovered that the Unit 2 "C" charging pump (Positive Displacement Pump) may require replacement of a control power fuse for the equipment to be available following certain postulated fires. 10CFR 50 Appendix "R" does not allow repair of hot shutdown equipment. The replacement of fuses is considered a repair. The "C" charging pump is relied on for Unit 2 charging following certain postulated fires. This situation could potentially leave Unit 2 without any charging pumps following certain postulated fires which would be outside the plants Appendix "R" design basis. Fire rounds will be instituted in affected fire zones until this issue is resolved.

The NRC Resident Inspector will be notified of this event by the licensee.


Power Reactor
Event Number: 36557
Facility: OCONEE
Region: 2     State: SC
Unit: [] [] [3]
RX Type: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-LP
NRC Notified By: MICHAEL DUNTON
HQ OPS Officer: JOHN MacKINNON
Notification Date: 01/03/2000
Notification Time: 14:13 [ET]
Event Date: 01/03/2000
Event Time: 12:57 [EST]
Last Update Date: 01/03/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
Person (Organization):
CHRIS CHRISTENSEN (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 A/R Y 55 Power Operation 0 Hot Standby
Event Text
MANUAL TURBINE TRIP FROM 28% CAUSED AN AUTOMATIC REACTOR TRIP

Unit 3 was initially at 100% power level when a Stator Coolant Runback initiated due to High Stator Coolant Temperature. Turbine Runback to 0 MWe with Reactor power at approximately 28% power. The Turbine was manually tripped and the Reactor automatically tripped on Turbine to Reactor anticipatory Trip. All rods fully inserted into the core. A couple of Once Through Steam Generator Safety Relief Valves opened/closed. Main Feedwater Water remained inservice and steam is being dumped to the condenser to maintain a Tave no load condition. All Emergency Core Cooling systems, Diesel generator, and their Keowee system are fully operable if needed.

The licensee believes that the Stator Water Cooling Temperature Control Valve (TCV) failed closed which caused the Stator water to bypass its coolers. The licensee also stated that it took approximately 3 to 4 minutes to reduce reactor power from 100% to 28% at which point the Turbine was manually tripped. The operators believed they were below the Turbine trip/Reactor Trip setpoint when the Main Turbine was manually tripped. One of the three Turbine Trip/Reactor Trip setpoint bypasses was bypassed but the other two were right on their bypass setpoint when the Turbine was manually tripped.


The NRC Resident Inspector was notified of this event by the licensee.

*** UPDATE ON 01/03/00 AT 1640 HOURS FROM DUNTON TAKEN BY MACKINNON ***

The licensee revised the above event report to state that the Turbine was manually tripped at 55% reactor power by orders of the SRO because of potential electrical damage to the generator. Therefore the licensee was expecting the reactor to automatically trip when the Turbine was manually tripped. R2DO (Chris Christensen) notified.

NRC Resident Inspector was notified of this update by the licensee.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 36558
Facility: FITZPATRICK
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: M ABRAMSKI
HQ OPS Officer: JOHN MacKINNON
Notification Date: 01/03/2000
Notification Time: 16:14 [ET]
Event Date: 01/03/2000
Event Time: 14:45 [EST]
Last Update Date: 01/25/2000
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(B) - POT RHR INOP 50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
JIMI YEROKUN (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE COOLANT INJECTION (HPCI) DECLARED INOPERABLE.

During Technical Specification required surveillance testing an oil leak was detected on a fitting in the HPCI hydraulic governor control system (EGR actuator). It was determined that had this leak developed during accident conditions, the HPCI system may not have been able to perform it's intended function for the duration of time required. The licensee entered the appropriate Technical Specification for declaring HPCI inoperable (7 day Limiting Condition of Operation). All other Emergency Core Cooling Systems and the Reactor Core Isolation Cooling system are fully operable if needed. The licensee is preparing to repair the HPCI hydraulic governor control system oil leak.

The NRC Resident Inspector was notified of this event by the licensee.

* * * RETRACTED AT 1412 EST ON 1/25/00 BY JAMES COSTEDIO TO FANGIE JONES * * *

The licensee has performed an engineering evaluation of the reported oil leak and determined that the amount of oil expected to be lost as a result would not have resulted in inadequate oil level. HPCI would have been able to perform its intended function for the duration of time required. Therefore, this event notification has been retracted.

The licensee notified the NRC Resident Inspector.

The R1DO (John Rogge) has been notified.