Event Notification Report for December 25, 1999
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
12/24/1999 - 12/25/1999
EVENT NUMBERS
36539
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 36539
Facility: PILGRIM
Region: 1 State: MA
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: BRIAN SULLIVAN
HQ OPS Officer: LEIGH TROCINE
Region: 1 State: MA
Unit: [1] [] []
RX Type: [1] GE-3
NRC Notified By: BRIAN SULLIVAN
HQ OPS Officer: LEIGH TROCINE
Notification Date: 12/25/1999
Notification Time: 07:45 [ET]
Event Date: 12/25/1999
Event Time: 07:00 [EST]
Last Update Date: 12/30/1999
Notification Time: 07:45 [ET]
Event Date: 12/25/1999
Event Time: 07:00 [EST]
Last Update Date: 12/30/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii) - DEGRAD COND DURING OP
10 CFR Section:
50.72(b)(1)(ii) - DEGRAD COND DURING OP
Person (Organization):
RICHARD CONTE (R1)
RICHARD CONTE (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOW SWITCHGEAR ROOM TEMPERATURE DUE TO DEGRADED HEATING, VENTILATION, AND AIR CONDITIONING (HVAC) COMPONENTS IN CONJUNCTION WITH COLD WEATHER
The following text is a portion of a facsimile received from the licensee:
"[The] 'A' switchgear room temperature [was] outside the [final safety analysis report] design temperature limit of 60°F. [The] temperature decreased to 59°F due to degraded [heating, ventilation, and air conditioning (HVAC)] components. No known operability issues have been identified."
The licensee stated that the temperature in the 'A' switchgear room has returned to 60°F but that cold weather is expected again tonight. The licensee is currently in the process of repairing the degraded HVAC components.
The licensee notified the NRC resident inspector.
* * * UPDATE AT 1045 ON 12/30/99 BY MANTENFEL, TAKEN BY WEAVER * * *
An engineering evaluation determined that the equipment remained operable at the as found temperature. The licensee is retracting this event. The NRC resident will be informed. The Operations center notified the RDO (Bellamy).
The following text is a portion of a facsimile received from the licensee:
"[The] 'A' switchgear room temperature [was] outside the [final safety analysis report] design temperature limit of 60°F. [The] temperature decreased to 59°F due to degraded [heating, ventilation, and air conditioning (HVAC)] components. No known operability issues have been identified."
The licensee stated that the temperature in the 'A' switchgear room has returned to 60°F but that cold weather is expected again tonight. The licensee is currently in the process of repairing the degraded HVAC components.
The licensee notified the NRC resident inspector.
* * * UPDATE AT 1045 ON 12/30/99 BY MANTENFEL, TAKEN BY WEAVER * * *
An engineering evaluation determined that the equipment remained operable at the as found temperature. The licensee is retracting this event. The NRC resident will be informed. The Operations center notified the RDO (Bellamy).