Power Reactor
Event Number: 36537
Facility: OCONEE
Region: 2 State: SC
Unit: [] [2] []
RX Type: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-LP
NRC Notified By: NEIL CONSTANCE
HQ OPS Officer: FANGIE JONES
Region: 2 State: SC
Unit: [] [2] []
RX Type: [1] B&W-L-LP,[2] B&W-L-LP,[3] B&W-L-LP
NRC Notified By: NEIL CONSTANCE
HQ OPS Officer: FANGIE JONES
Notification Date: 12/24/1999
Notification Time: 03:02 [ET]
Event Date: 12/24/1999
Event Time: 02:07 [EST]
Last Update Date: 12/24/1999
Notification Time: 03:02 [ET]
Event Date: 12/24/1999
Event Time: 02:07 [EST]
Last Update Date: 12/24/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
Person (Organization):
BRUCE MALLETT (R2)
BRUCE MALLETT (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | A/R | Y | 77 | Power Operation | 0 | Hot Standby |
REACTOR TRIP ON HIGH REACTOR COOLANT SYSTEM PRESSURE (Refer to event #36532 for a similar event that occurred on 12/21/99.)
"Unit 2 tripped on RCS high pressure at 0207 [EST]. The RPS setpoint of 2345 psig was exceeded, resulting in an RPS actuation and tripping all CRD breakers. The initiating event was a spurious closure of all main turbine intercept/reheat stop valves and main turbine control valves. The plant is stable in Mode 3, with a trip investigation in progress."
No primary power-operated relief valves (setpoint 2405 psig) or code safety valves lifted. Secondary side code safeties lifted as expected on the trip, and all valves shut with the turbine bypass valves in operation to remove decay heat to the main condenser. Main feedwater is maintaining steam generator level.
The NRC resident inspector was notified.
(Call the NRC operations officer for additional information.)
"Unit 2 tripped on RCS high pressure at 0207 [EST]. The RPS setpoint of 2345 psig was exceeded, resulting in an RPS actuation and tripping all CRD breakers. The initiating event was a spurious closure of all main turbine intercept/reheat stop valves and main turbine control valves. The plant is stable in Mode 3, with a trip investigation in progress."
No primary power-operated relief valves (setpoint 2405 psig) or code safety valves lifted. Secondary side code safeties lifted as expected on the trip, and all valves shut with the turbine bypass valves in operation to remove decay heat to the main condenser. Main feedwater is maintaining steam generator level.
The NRC resident inspector was notified.
(Call the NRC operations officer for additional information.)