Skip to main content

Event Notification Report for November 30, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
11/29/1999 - 11/30/1999

EVENT NUMBERS
3647436475

Power Reactor
Event Number: 36474
Facility: WOLF CREEK
Region: 4     State: KS
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: DALE BERRY
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 11/30/1999
Notification Time: 06:12 [ET]
Event Date: 11/30/1999
Event Time: 04:59 [CST]
Last Update Date: 11/30/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(i)(A) - PLANT S/D REQD BY TS
Person (Organization):
DALE POWERS (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
-TS REQD PLANT S/D DUE TO FAILED ESFAS AFW ACTUATION LOGIC RELAY 48 VDC POWER SUPPLY-

THE LICENSEE DISCOVERED A FAILED 48 VDC POWER SUPPLY FOR THE BALANCE OF PLANT ENGINEERED SAFETY FEATURE ACTUATION SYSTEM (ESFAS) AUTOMATIC ACTUATION LOGIC RELAYS FOR THE TRAIN 'A' AUXILIARY FEEDWATER (AFW) SYSTEM. TECH SPEC 3.3.2, FUNCTION 6.C, ACTION 21, REQUIRES THE LICENSEE TO RESTORE THE POWER SUPPLY TO OPERABLE STATUS OR TO PLACE THE PLANT IN HOT STANDBY MODE IN 6 HOURS AND HOT SHUTDOWN MODE IN THE FOLLOWING 6 HOURS.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR AND PLANS TO ISSUE A PRESS RELEASE.

* * * UPDATE AT 0837 ON 11/30/99 BY DAVE DEES TO JOLLIFFE * * *

AT 0724 CST, THE LICENSEE DISCOVERED THAT THE OVERVOLTAGE CUTOUT SETPOINT ON THE POWER SUPPLY HAD DRIFTED LOW AND DEENERGIZED THE POWER SUPPLY. THE LICENSEE ADJUSTED THE SETPOINT TO ITS PROPER VALUE, RESTORED THE POWER SUPPLY TO SERVICE, DECLARED IT OPERABLE, STOPPED THE POWER REDUCTION AT 31% POWER, EXITED THE TECH SPEC ACTION STATEMENT, AND BEGAN INCREASING POWER.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.

THE NRC OPERATIONS OFFICER NOTIFIED THE R4DO DALE POWERS.

SEE EVENT # 36476 FOR TECH SPEC REQUIRED SHUTDOWN.


Power Reactor
Event Number: 36475
Facility: SAINT LUCIE
Region: 2     State: FL
Unit: [1] [2] []
RX Type: [1] CE,[2] CE
NRC Notified By: DAVE WILLIAMS
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 11/30/1999
Notification Time: 11:02 [ET]
Event Date: 11/30/1999
Event Time: 10:05 [EST]
Last Update Date: 11/30/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
LEN WERT (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 100 Power Operation 100 Power Operation
Event Text
- Florida DEP notified about an injured loggerhead sea turtle removed from the plant intake canal -

At 1005 on 11/30/99, the licensee notified the Florida Department of Environmental Protection (DEP) regarding the removal of an injured adult female loggerhead sea turtle from the plant intake canal. The injuries are not believed to be related to plant operation. The licensee plans to transfer the turtle to a rehabilitation facility.

The licensee notified the NRC Resident Inspector.