Power Reactor
Event Number: 36471
Facility: PALISADES
Region: 3     State: MI
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: DALE ENGLE
HQ OPS Officer: STEVE SANDIN
Notification Date: 11/28/1999
Notification Time: 19:50 [ET]
Event Date: 11/28/1999
Event Time: 15:45 [EST]
Last Update Date: 12/05/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - DEG/UNANALYZED COND
Person (Organization):
RONALD GARDNER (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
"B" TRAIN LOW PRESSURE SAFETY INJECTION (LPSI) FLOW RATES FOUND DEGRADED DURING SURVEILLANCE TESTING.

"WHILE PERFORMING QO-8B (LOW PRESSURE SAFETY INJECTION FLOW TESTING), IT WAS DETERMINED THAT FLOW TO TWO (2) OF FOUR (4) LOOPS (VALVES-MO-3012 & MO-3014 [RIGHT CHANNEL]) WAS INADEQUATE. THE FLOW RATES WERE BELOW THE DESIGN BASIS FOR ACCIDENT CONDITIONS. [THIS] CONDITION WAS DISCOVERED DURING SURVEILLANCE TESTING WHILE THE PLANT WAS IN COLD SHUTDOWN. THIS IS REPORTABLE PER 50.72(b)(2)(I)."

THE DESIGN FLOW RATE IS 1720 GPM. THE AS-FOUND FLOW RATES THROUGH VALVES 3012 & 3014 WERE 1650 AND 1500 GPM, RESPECTIVELY. THE "B" TRAIN LPSI HAS BEEN DECLARED INOPERABLE PENDING CORRECTIVE ACTION WHICH IS TO BE DETERMINED. THE UNIT IS NOT IN A TECH SPEC ACTION STATEMENT IN THAT LPSI IS NOT REQUIRED FOR CURRENT PLANT CONDITIONS. THE SURVEILLANCE TEST WHICH IDENTIFIED THIS CONDITION IS PERFORMED EACH REFUELING OUTAGE (APPROXIMATELY EVERY 18 MONTHS). THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.

* * * RETRACTED AT 1813 EST ON 12/5/99 BY ROBERT VINCENT TO FANGIE JONES * * *

The licensee conducted extensive testing and analysis to better model accidents and the performance of the LPSI system. They have determined that the LPSI system flow rates are capable of meeting the requirements of accident mitigation and are retracting this event notification.

The licensee notified the NRC Resident Inspector and the NRC Headquarters Operations Officer notified the R3DO (Geoffrey Wright).