Power Reactor
Event Number: 36454
Facility: GRAND GULF
Region: 4     State: MS
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: DAVID HANKS
HQ OPS Officer: FANGIE JONES
Notification Date: 11/20/1999
Notification Time: 08:51 [ET]
Event Date: 11/20/1999
Event Time: 07:30 [CST]
Last Update Date: 11/20/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
BILL JONES (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
EMERGENCY OPERATIONS FACILITY (EOF) LOST POWER FOR 1.5 HOURS DURING POWER SUPPLY SHIFT

This licensee made this notification as an information call.

The backup emergency diesel generator (EDG) for the EOF failed to automatically start when offsite power was lost during a planned transfer of power. The offsite power supply breaker hung during the transfer causing the loss of power and the backup EDG did not start. The licensee is investigating both problems.

The licensee intends to notify the NRC Resident Inspection.