Skip to main content

Event Notification Report for September 27, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/26/1999 - 09/27/1999

EVENT NUMBERS
3623336236

Power Reactor
Event Number: 36233
Facility: ROBINSON
Region: 2     State: SC
Unit: [2] [] []
RX Type: [2] W-3-LP
NRC Notified By: DON KNIGHT
HQ OPS Officer: BOB STRANSKY
Notification Date: 09/28/1999
Notification Time: 00:47 [ET]
Event Date: 09/27/1999
Event Time: 22:33 [EDT]
Last Update Date: 09/28/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
THOMAS DECKER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
NORMAL POWER SUPPLY TO EMERGENCY ELECTRICAL BUS LOST DUE TO PERSONNEL ERROR

Emergency bus E2 was temporarily deenergized after a plant worker bumped 4kV breaker 5215, the normal supply breaker to the bus, causing it to trip. The B emergency diesel generator (EDG) automatically started due to an undervoltage condition on bus E2 and loaded to the bus, restoring power. The licensee reported that the operating residual heat removal (RHR) pump stopped running due to the loss of power to bus E2, but operators manually started the standby pump and restored shutdown cooling within 2 minutes. Reactor coolant system temperature did not increase appreciably during the alignment of the standby RHR pump.

The EDG continues to supply power to bus E2 while the licensee makes preparations to transfer back to the normal power supply. The NRC resident inspector has been informed of this event by the licensee.


Fuel Cycle Facility
Event Number: 36236
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: JOE HALCOMB
HQ OPS Officer: LEIGH TROCINE
Notification Date: 09/28/1999
Notification Time: 12:24 [ET]
Event Date: 09/27/1999
Event Time: 16:09 [EDT]
Last Update Date: 09/28/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
TONY VEGEL (R3)
JOSIE PICCONE (NMSS)
Event Text
VALID ACTUATION OF A 'Q' SAFETY SYSTEM (24-hour report)

The following text is a portion of a facsimile received from Portsmouth:

"On 09/27/99 at 1609 hours, the X-333 Cascade Building operation personnel received three cascade automatic data processing (CADP) smoke head alarm actuations. These smoke heads were monitoring operating cell 33-2-4 which was promptly taken off stream and shut down. Emergency response personnel monitored the area, and all air sample results for hydrogen fluoride and UF6 were below detectable levels."

"This event is reportable due to the valid actuation of a 'Q' safety system."

"This event is reportable to the NRC per Safety Analysis Report (SAR) Section 6.9, Table 6.9-1. This is a 24-hour reportable event."

"There was no loss of hazardous/radioactive material or radioactive/radiological contamination exposure as a result of this event."

Portsmouth personnel notified the NRC resident inspector and plan to notify the Department of Energy site representative.