Skip to main content

Event Notification Report for September 21, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/20/1999 - 09/21/1999

EVENT NUMBERS
36203362043620536206

Power Reactor
Event Number: 36203
Facility: THREE MILE ISLAND
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] B&W-L-LP,[2] B&W-L-LP
NRC Notified By: BOYER
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 09/21/1999
Notification Time: 00:56 [ET]
Event Date: 09/21/1999
Event Time: 00:50 [EDT]
Last Update Date: 09/21/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(v) - OFFSITE MEDICAL
Person (Organization):
ROBERT SUMMERS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Refueling 0 Refueling
Event Text
POTENTIALLY CONTAMINATED INJURED PERSON TRANSPORTED OFFSITE.

THE LICENSEE TRANSPORTED AN INDIVIDUAL , WHO INJURED HIS LOWER BACK WHILE WORKING INSIDE CONTAINMENT ON THE UPPER MANWAY, TO THE HERSHEY MEDICAL CENTER. HE MAY HAVE BEEN CONTAMINATED, SO HE WAS ACCOMPANIED BY HEALTH PHYSICS PERSONNEL TO THE HOSPITAL.

THE RESIDENT INSPECTOR WILL BE NOTIFIED

*** UPDATE ON 9/21/99 @ 0209 BY BOYER TO GOULD ***

THE INDIVIDUAL WAS NOT CONTAMINATED, HOWEVER, HIS CLOTHING WAS AND IT IS BEING RETURNED TO THE SITE.

THE RESIDENT INSPECTOR WAS NOTIFIED.


Power Reactor
Event Number: 36204
Facility: FERMI
Region: 3     State: MI
Unit: [2] [] []
RX Type: [2] GE-4
NRC Notified By: ARAB
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 09/21/1999
Notification Time: 08:04 [ET]
Event Date: 09/21/1999
Event Time: 04:38 [EDT]
Last Update Date: 09/21/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
ROGER LANKSBURY (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 97 Power Operation 97 Power Operation
Event Text
HPCI DECLARED INOPERABLE

During performance of the calibration/functional surveillance test of the HPCI equipment room temperature instrumentation, the trip unit being tested failed upscale. A step in the surveillance procedure places a keylock
switch in the TEST position, preventing a HPCI system Channel B isolation and HPCI Turbine Trip. The trip unit was declared inoperable.

Fermi 2 Technical Specifications require that the inoperable instrument channel be restored to OPERABLE status in 6 hours or that the ACTION be performed to close the affected system isolation valves within 1 hour and declare the system inoperable.

On September 21, 1999 at 0438 hours, the affected HPCI isolation valves were isolated and the HPCI system was declared inoperable, putting the plant in a 14 day LCO action statement.

Efforts to replace the failed trip unit are in progress.

The NRC Resident Inspector was notified.


Fuel Cycle Facility
Event Number: 36205
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: RICK LARSON
HQ OPS Officer: WILLIAM POERTNER
Notification Date: 09/21/1999
Notification Time: 11:28 [ET]
Event Date: 09/21/1999
Event Time: 10:08 [EDT]
Last Update Date: 09/21/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
ROGER LANKSBURY (R3)
JOSIE PICCONE (NMSS)
Event Text
OFFSITE NOTIFICATION DUE TO SANITARY WATER SUPPLY LINE RUPTURE.

At approximately 1008 hours on 9/21/99, the Ohio EPA and the National Response Center were notified of a sanitary water supply line rupture from one of the plant's 24 inch sanitary water supply lines. This rupture may have an effect on the environment as sanitary water (Drinking Water) enters local water sheds. Follow-up notifications were made to the above agencies to inform them that the leak was isolated at 1040 hours.

There was no loss of hazardous/radioactive material or radioactive/radiological contamination exposure as a result of this event.

The NRC Resident has been notified.


Power Reactor
Event Number: 36206
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [2] [] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: JOHN BALLETTA
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 09/21/1999
Notification Time: 15:30 [ET]
Event Date: 09/21/1999
Event Time: 14:00 [EDT]
Last Update Date: 09/21/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - DEG/UNANALYZED COND
Person (Organization):
ROBERT SUMMERS (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N N 0 Hot Shutdown 0 Hot Shutdown
Event Text
-SECTION OF FIRE PROTECTION PIPING NOT SEISMICALLY SUPPORTED PER NRC INFO NOTICE 98-31-

A CONTRACTOR ASSISTING THE LICENSEE WITH A REVIEW OF FIRE PROTECTION SYSTEM PIPING
WITH RESPECT TO INFORMATION OUTLINED IN NRC INFORMATION NOTICE 98-31 IDENTIFIED POTENTIALLY HIGH IMPACT LOADS ON A FOUR INCH DIAMETER SECTION OF FIRE PROTECTION SYSTEM PIPING IN THE PRIMARY AUXILIARY BUILDING. HIGH IMPACT LOADS COULD BE IMPOSED ON THE VICTAULIC COUPLINGS ON THE PIPING DURING A SEISMIC EVENT.

FAILURE OF THIS PIPING COULD CAUSE FLOODING IN THE LOWER LEVEL OF THE PRIMARY AUXILIARY BUILDING WHICH INCLUDES THE RHR PUMPS. WITHIN THE NEXT 24 HOURS, THE LICENSEE PLANS TO INSTALL TWO ADDITIONAL PIPE SUPPORTS ON THIS SECTION OF PIPING TO LIMIT PIPE DISPLACEMENT AND TO LIMIT THE POTENTIAL FOR IMPACT LOADING ON THIS SECTION OF PIPING.

THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.