Event Notification Report for September 12, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/11/1999 - 09/12/1999

EVENT NUMBERS
361483614936150

Power Reactor
Event Number: 36148
Facility: SOUTH TEXAS
Region: 4     State: TX
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: GREG JANAK
HQ OPS Officer: FANGIE JONES
Notification Date: 09/12/1999
Notification Time: 06:31 [ET]
Event Date: 09/12/1999
Event Time: 03:44 [CDT]
Last Update Date: 09/12/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
GARY SANBORN (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP DURING TURBINE TRIP SYSTEM TESTING

During the performance of Main Turbine Emergency Trip System testing on Channel 1, the plant experienced an automatic turbine trip which initiated a reactor trip. All control rods fully inserted and systems responded as expected including the start of the Auxiliary Feedwater System, an Engineered Safety Feature system. No relief valves or safety valves opened and excess energy is being released via steam to the main condensers. The licensee is investigating exact cause of trip.

The licensee notified the NRC Resident Inspector.


Power Reactor
Event Number: 36149
Facility: NORTH ANNA
Region: 2     State: VA
Unit: [1] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: VICKY HARTE
HQ OPS Officer: FANGIE JONES
Notification Date: 09/12/1999
Notification Time: 09:30 [ET]
Event Date: 09/12/1999
Event Time: 09:04 [EDT]
Last Update Date: 09/15/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - ENS INOPERABLE
Person (Organization):
ROBERT HAAG (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 60 Power Operation 60 Power Operation
2 N N 0 Hot Standby 0 Hot Standby
Event Text
LOST SAFETY PARAMETER DISPLAY SYSTEM AND THE TECHNICAL SUPPORT CENTER COMPUTER

Power was lost to the Safety Parameter Display System (SPDS) and the Technical Support Center (TSC) computer system at 0904 EDT on 9/12/99. The bus supplying power to the battery charger for the SPDS and TSC computer was lost when the supply breaker opened on a ground detection, on the underground cable supply. The normal alternate power supply to the battery charger was previously lost, some time ago, due to another ground on its underground cable supply. The licensee made the decision to preserve the battery and deenergized the battery bus. Also, with the TSC computer system out-of-service, the control room will serve as the alternate TSC facility.

This event is a major loss of emergency assessment capability and is reportable. Troubleshooting and repairs to the electrical distribution system are in progress. Also, the licensee is investigating an alternate methods to power the battery charger.

The licensee notified the NRC Resident Inspector.


***Update on 09/15/99 at 1255ET by Kemp taken by MacKinnon***

Power was restored to the TSC and the SPDS was restored to service at 1132ET today (09/15/99). R2DO (Chris Christensen) notified.

The NRC Resident Inspector will be informed by the licensee of this update.


Power Reactor
Event Number: 36150
Facility: PEACH BOTTOM
Region: 1     State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: RICHARD TRUAX
HQ OPS Officer: WILLIAM POERTNER
Notification Date: 09/12/1999
Notification Time: 16:17 [ET]
Event Date: 09/12/1999
Event Time: 15:30 [EDT]
Last Update Date: 09/13/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
Person (Organization):
TOM MOSLAK (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
3 N Y 85 Power Operation 85 Power Operation
Event Text
LOSS OF POWER TO THE TSC DUE TO BREAKER FAILURE.

During planned electrical switching at the Unit 1 training center a breaker failed to close causing a loss of power to the Unit 1 training center which provides power to the Technical Support Center (TSC). This resulted in a loss of assessment capability from the TSC . Assessment capability is still available from the main control room and Emergency Operation Facility.

The licensee is investigating the cause of the breaker failure.

The NRC resident will be notified.

* * * UPDATE AT 0155 EDT ON 9/13/99 BY ED EILOLA TO FANGIE JONES * * *

Repairs were made and power was restored to the TSC at 0145 EDT on 9/13/99. The licensee intends to notify the NRC Resident Inspector. The NRC operations officer notified the R1DO (Tom Moslak).