Event Notification Report for September 06, 1999
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
09/05/1999 - 09/06/1999
Power Reactor
Event Number: 36129
Facility: SAINT LUCIE
Region: 2 State: FL
Unit: [1] [2] []
RX Type: [1] CE,[2] CE
NRC Notified By: STEVE MERRILL
HQ OPS Officer: LEIGH TROCINE
Region: 2 State: FL
Unit: [1] [2] []
RX Type: [1] CE,[2] CE
NRC Notified By: STEVE MERRILL
HQ OPS Officer: LEIGH TROCINE
Notification Date: 09/06/1999
Notification Time: 02:25 [ET]
Event Date: 09/06/1999
Event Time: 02:00 [EDT]
Last Update Date: 09/07/1999
Notification Time: 02:25 [ET]
Event Date: 09/06/1999
Event Time: 02:00 [EDT]
Last Update Date: 09/07/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
KERRY LANDIS (R2)
KERRY LANDIS (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
PLANNED OFFSITE NOTIFICATION DUE TO DISCOVERY OF A DEAD SEA TURTLE IN THE INTAKE CANAL
At 0200, the licensee recovered a dead sea turtle from the plant's intake canal. In accordance with the licensee's marine turtle permit, the land utilization department plans to notify the Department of Environmental Protection's Bureau of Protected Species within 12 hours.
The licensee also plans to notify the NRC resident inspector.
* * * UPDATE 1226 EDT ON 9/7/99 FROM CALVIN WARD TO S. SANDIN * * *
OFFSITE NOTIFICATION TO FLORIDA AGENCY INVOLVING ADDITIONAL DEAD SEA TURTLE
"A dead sea turtle was recovered from the St. Lucie plant intake canal at approximately 0800 hours on 9/7/99. The Florida Department of Environmental Protection was notified at 0854 hours as required by the St. Lucie plant sea turtle permit. This notification to a state government agency requires a 4-hour non-emergency notification to the NRC per 10CFR50.72(b)(2)(vi)."
The licensee informed the NRC resident inspector. Notified R2DO (Haag).
At 0200, the licensee recovered a dead sea turtle from the plant's intake canal. In accordance with the licensee's marine turtle permit, the land utilization department plans to notify the Department of Environmental Protection's Bureau of Protected Species within 12 hours.
The licensee also plans to notify the NRC resident inspector.
* * * UPDATE 1226 EDT ON 9/7/99 FROM CALVIN WARD TO S. SANDIN * * *
OFFSITE NOTIFICATION TO FLORIDA AGENCY INVOLVING ADDITIONAL DEAD SEA TURTLE
"A dead sea turtle was recovered from the St. Lucie plant intake canal at approximately 0800 hours on 9/7/99. The Florida Department of Environmental Protection was notified at 0854 hours as required by the St. Lucie plant sea turtle permit. This notification to a state government agency requires a 4-hour non-emergency notification to the NRC per 10CFR50.72(b)(2)(vi)."
The licensee informed the NRC resident inspector. Notified R2DO (Haag).
Power Reactor
Event Number: 36130
Facility: TURKEY POINT
Region: 2 State: FL
Unit: [3] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: SAM SHAFER
HQ OPS Officer: STEVE SANDIN
Region: 2 State: FL
Unit: [3] [4] []
RX Type: [3] W-3-LP,[4] W-3-LP
NRC Notified By: SAM SHAFER
HQ OPS Officer: STEVE SANDIN
Notification Date: 09/06/1999
Notification Time: 18:25 [ET]
Event Date: 09/06/1999
Event Time: 17:35 [EDT]
Last Update Date: 09/06/1999
Notification Time: 18:25 [ET]
Event Date: 09/06/1999
Event Time: 17:35 [EDT]
Last Update Date: 09/06/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
Person (Organization):
KERRY LANDIS (R2)
KERRY LANDIS (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 3 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 4 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF EMERGENCY RESPONSE CAPABILITY DUE TO POWER LINE BLOCKING MAIN PLANT ACCESS.
"LOSS OF OFFSITE RESPONSE CAPABILITY. REPORTS RECEIVED OF ENERGIZED POWER LINE FELL ACROSS MAIN PLANT ACCESS ROAD TO PLANT SITE. PLANT ACCESS RESTORED AT 1820 EDT ON 9/6/99."
THE CONTROL ROOM WAS NOTIFIED AT 1735 EDT OF THE LINE BLOCKING ACCESS TO THE SITE. TRANSMISSION & DISTRIBUTION (T&D) REPORTED THAT THE FELLED LINE WAS REMOVED AT 1820 EDT.
THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.
"LOSS OF OFFSITE RESPONSE CAPABILITY. REPORTS RECEIVED OF ENERGIZED POWER LINE FELL ACROSS MAIN PLANT ACCESS ROAD TO PLANT SITE. PLANT ACCESS RESTORED AT 1820 EDT ON 9/6/99."
THE CONTROL ROOM WAS NOTIFIED AT 1735 EDT OF THE LINE BLOCKING ACCESS TO THE SITE. TRANSMISSION & DISTRIBUTION (T&D) REPORTED THAT THE FELLED LINE WAS REMOVED AT 1820 EDT.
THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.
Power Reactor
Event Number: 36131
Facility: BEAVER VALLEY
Region: 1 State: PA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: MATTHEW MORGAN
HQ OPS Officer: STEVE SANDIN
Region: 1 State: PA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: MATTHEW MORGAN
HQ OPS Officer: STEVE SANDIN
Notification Date: 09/06/1999
Notification Time: 19:08 [ET]
Event Date: 09/06/1999
Event Time: 17:22 [EDT]
Last Update Date: 09/06/1999
Notification Time: 19:08 [ET]
Event Date: 09/06/1999
Event Time: 17:22 [EDT]
Last Update Date: 09/06/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
JOHN ROGGE (R1)
JOHN ROGGE (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | M/R | Y | 100 | Power Operation | 0 | Hot Standby |
UNIT 1 WAS MANUALLY TRIPPED FROM 100% POWER AFTER RECEIVING MAIN GENERATOR FIELD ALARMS
"BEAVER VALLEY POWER STATION (BVPS) UNIT ONE PERFORMED A MANUAL REACTOR TRIP DUE TO RECEIVING MAIN GENERATOR FIELD ALARMS. MAIN GENERATOR POWER FACTOR WAS OBSERVED TO BE SWINGING PRIOR TO THE TRIP.
"UNIT ONE IS CURRENTLY STABLE IN MODE 3. NO OTHER PROBLEMS OCCURRED DURING THE EVENT. THE AUXILIARY FEED PUMPS AUTOMATICALLY STARTED AS EXPECTED DUE TO LOW STEAM GENERATOR LEVEL AFTER THE REACTOR TRIP.
"THE CAUSE OF THE MAIN GENERATOR PROBLEM IS NOT YET KNOWN. AN EVENT RESPONSE TEAM IS BEING FORMED TO INVESTIGATE THE PROBLEM."
ALL CONTROL RODS FULLY INSERTED FOLLOWING THE REACTOR TRIP. NO PRIMARY OR SECONDARY SAFETY OR RELIEF VALVES LIFTED. UNIT 1 IS PRESENTLY STABLE IN MODE 3 WITH DECAY HEAT BEING REJECTED TO THE MAIN CONDENSER . THE UNIT 1 EMERGENCY DIESEL GENERATORS ARE AVAILABLE IF NEEDED. PRELIMINARY INDICATION IS THAT THE MAIN GENERATOR EXCITER VOLTAGE MALFUNCTIONED. UNIT 2 WAS UNAFFECTED.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.
"BEAVER VALLEY POWER STATION (BVPS) UNIT ONE PERFORMED A MANUAL REACTOR TRIP DUE TO RECEIVING MAIN GENERATOR FIELD ALARMS. MAIN GENERATOR POWER FACTOR WAS OBSERVED TO BE SWINGING PRIOR TO THE TRIP.
"UNIT ONE IS CURRENTLY STABLE IN MODE 3. NO OTHER PROBLEMS OCCURRED DURING THE EVENT. THE AUXILIARY FEED PUMPS AUTOMATICALLY STARTED AS EXPECTED DUE TO LOW STEAM GENERATOR LEVEL AFTER THE REACTOR TRIP.
"THE CAUSE OF THE MAIN GENERATOR PROBLEM IS NOT YET KNOWN. AN EVENT RESPONSE TEAM IS BEING FORMED TO INVESTIGATE THE PROBLEM."
ALL CONTROL RODS FULLY INSERTED FOLLOWING THE REACTOR TRIP. NO PRIMARY OR SECONDARY SAFETY OR RELIEF VALVES LIFTED. UNIT 1 IS PRESENTLY STABLE IN MODE 3 WITH DECAY HEAT BEING REJECTED TO THE MAIN CONDENSER . THE UNIT 1 EMERGENCY DIESEL GENERATORS ARE AVAILABLE IF NEEDED. PRELIMINARY INDICATION IS THAT THE MAIN GENERATOR EXCITER VOLTAGE MALFUNCTIONED. UNIT 2 WAS UNAFFECTED.
THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.