Event Notification Report for September 04, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
09/03/1999 - 09/04/1999

EVENT NUMBERS
36127

Power Reactor
Event Number: 36127
Facility: NORTH ANNA
Region: 2     State: VA
Unit: [1] [2] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: VICKY HARTE
HQ OPS Officer: WILLIAM POERTNER
Notification Date: 09/04/1999
Notification Time: 18:53 [ET]
Event Date: 09/04/1999
Event Time: 16:00 [EDT]
Last Update Date: 09/04/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(C) - POT UNCNTRL RAD REL
Person (Organization):
KERRY LANDIS (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 88 Power Operation 88 Power Operation
Event Text
DEGRADED SAFEGUARDS AREA EXHAUST SYSTEM DUE TO MISSING DAMPER SEALS.

On 9/4/99, at 1600, it was discovered that a damper associated with the Auxiliary Building General Exhaust Ventilation System was degraded due to missing damper seals. This damper is located on the inlet of the Auxiliary Building Charcoal Filter Bank which is a common filter used to filter various area exhaust streams when required. The Safeguards Area Exhaust system automatically aligns to the common filter bank on a Containment Depressurization Actuation System signal to ensure filtration of any ECCS and ESF component leakage in the Safeguards Area atmosphere that may develop from a Large Break LOCA. The degraded damper in the Auxiliary Building General Area Exhaust System had the potential to cause a flow path that could have resulted in a portion of the Safeguards Area Exhaust flow to bypass the Charcoal Filter prior to release to the Environment. The potential bypass flow path would still be monitored by the Radiation Monitoring System. The area can be manually aligned to the charcoal filters. The bypass flow path would be considered a degradation of the Ventilation System to the extent that the fulfillment of the safety function of the Safeguards Area Exhaust System may have been adversely affected. Action taken during the troubleshooting of ventilation flow eliminated the bypass flow path. Administrative controls have been established to prevent unfiltered release of the Safeguards Area Exhaust System during accident conditions.

Maintenance is in progress to repair the damper.

The NRC resident has been notified.