Event Notification Report for August 14, 1999
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
08/13/1999 - 08/14/1999
EVENT NUMBERS
36034360353603636031
Power Reactor
Event Number: 36034
Facility: SUSQUEHANNA
Region: 1 State: PA
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: GRANT FERNSLER
HQ OPS Officer: DICK JOLLIFFE
Region: 1 State: PA
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: GRANT FERNSLER
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 08/14/1999
Notification Time: 15:54 [ET]
Event Date: 08/14/1999
Event Time: 15:00 [EDT]
Last Update Date: 08/16/1999
Notification Time: 15:54 [ET]
Event Date: 08/14/1999
Event Time: 15:00 [EDT]
Last Update Date: 08/16/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
Person (Organization):
HAROLD GRAY (R1DO)
HAROLD GRAY (R1DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
UNAVAILABILITY OF NOTIFICATION SYSTEMS FOR PAGER ACTIVATION
The tele-notification system utilized for pager activation and the backup alpha-mate paging system were not available. Manual paging was available for emergency notification.
The licensee plans to notify the NRC resident inspector.
The tele-notification system utilized for pager activation and the backup alpha-mate paging system were not available. Manual paging was available for emergency notification.
The licensee plans to notify the NRC resident inspector.
Power Reactor
Event Number: 36035
Facility: PEACH BOTTOM
Region: 1 State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: PAT NAVIN
HQ OPS Officer: DICK JOLLIFFE
Region: 1 State: PA
Unit: [2] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: PAT NAVIN
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 08/14/1999
Notification Time: 20:41 [ET]
Event Date: 08/14/1999
Event Time: 20:05 [EDT]
Last Update Date: 08/16/1999
Notification Time: 20:41 [ET]
Event Date: 08/14/1999
Event Time: 20:05 [EDT]
Last Update Date: 08/16/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - EMERGENCY SIREN INOP
10 CFR Section:
50.72(b)(1)(v) - EMERGENCY SIREN INOP
Person (Organization):
HAROLD GRAY (R1DO)
HAROLD GRAY (R1DO)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 3 | N | Y | 95 | Power Operation | 95 | Power Operation |
UNAVAILABILITY OF THE EMERGENCY NOTIFICATION SYSTEM (ENS) LINE AND 16 EVACUATION SIRENS
The licensee reported that the emergency notification system line was out of service as well as 14 of 26 evacuation sirens in York County and 2 of 35 evacuation sirens in Lancaster County.
The licensee plans to notify the NRC resident inspector.
The licensee reported that the emergency notification system line was out of service as well as 14 of 26 evacuation sirens in York County and 2 of 35 evacuation sirens in Lancaster County.
The licensee plans to notify the NRC resident inspector.
Power Reactor
Event Number: 36036
Facility: HARRIS
Region: 2 State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: MAURICE GRIFFIN
HQ OPS Officer: LEIGH TROCINE
Region: 2 State: NC
Unit: [1] [] []
RX Type: [1] W-3-LP
NRC Notified By: MAURICE GRIFFIN
HQ OPS Officer: LEIGH TROCINE
Notification Date: 08/16/1999
Notification Time: 21:06 [ET]
Event Date: 08/14/1999
Event Time: 16:00 [EDT]
Last Update Date: 08/18/1999
Notification Time: 21:06 [ET]
Event Date: 08/14/1999
Event Time: 16:00 [EDT]
Last Update Date: 08/18/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - EMERGENCY SIREN INOP
10 CFR Section:
50.72(b)(1)(v) - EMERGENCY SIREN INOP
Person (Organization):
CHARLES OGLE (R2)
CHARLES OGLE (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
LOSS OF EMERGENCY SIRENS IN HARNETT COUNTY DUE TO A LIGHTNING STRIKE
The following text is a portion of a facsimile received from the licensee:
"All sirens in Harnett County were lost from 1600 to 1730 on 08/14/99 ... due to a lightning strike [that took out a 911 repeater]. The backup repeater was placed in service at 1730 [on 08/14/99]. The primary repeater was placed in service at 1200 on 08/16/99. The backup repeater is not tested routinely, and it is unknown if it would have actuated the sirens from 1730 [on] 08/14/99 until 1200 [on] 08/16/99. This feature will be tested tomorrow to determine if the sirens were operable on the backup repeater."
The licensee stated that there are a total of 81 sirens associated with the Harris facility and that all 7 sirens in Harnett County were lost. This event was determined to be reportable at 2040 on 08/16/99.
The licensee plans to notify the NRC resident inspector.
******************** UPDATE AT 1606 ON 08/18/99 FROM MARK ELLINGTON TO TROCINE ********************
The following text is a portion of a facsimile received from the licensee:
"A test signal was successfully transmitted to and received by the Harnett County sirens on 08/17/99 at 0740 using the current configuration. This test verifies that the siren system was operable when the primary repeater was returned to service at 1200 on 08/16/99. No additional testing with the backup repeater is planned."
The licensee notified the NRC resident inspector. The NRC operations officer notified the R2DO (Barr).
The following text is a portion of a facsimile received from the licensee:
"All sirens in Harnett County were lost from 1600 to 1730 on 08/14/99 ... due to a lightning strike [that took out a 911 repeater]. The backup repeater was placed in service at 1730 [on 08/14/99]. The primary repeater was placed in service at 1200 on 08/16/99. The backup repeater is not tested routinely, and it is unknown if it would have actuated the sirens from 1730 [on] 08/14/99 until 1200 [on] 08/16/99. This feature will be tested tomorrow to determine if the sirens were operable on the backup repeater."
The licensee stated that there are a total of 81 sirens associated with the Harris facility and that all 7 sirens in Harnett County were lost. This event was determined to be reportable at 2040 on 08/16/99.
The licensee plans to notify the NRC resident inspector.
******************** UPDATE AT 1606 ON 08/18/99 FROM MARK ELLINGTON TO TROCINE ********************
The following text is a portion of a facsimile received from the licensee:
"A test signal was successfully transmitted to and received by the Harnett County sirens on 08/17/99 at 0740 using the current configuration. This test verifies that the siren system was operable when the primary repeater was returned to service at 1200 on 08/16/99. No additional testing with the backup repeater is planned."
The licensee notified the NRC resident inspector. The NRC operations officer notified the R2DO (Barr).
Power Reactor
Event Number: 36031
Facility: PEACH BOTTOM
Region: 1 State: PA
Unit: [] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: BOB BIRMINGHAM
HQ OPS Officer: STEVE SANDIN
Region: 1 State: PA
Unit: [] [3] []
RX Type: [2] GE-4,[3] GE-4
NRC Notified By: BOB BIRMINGHAM
HQ OPS Officer: STEVE SANDIN
Notification Date: 08/14/1999
Notification Time: 05:35 [ET]
Event Date: 08/14/1999
Event Time: 04:35 [EDT]
Last Update Date: 08/14/1999
Notification Time: 05:35 [ET]
Event Date: 08/14/1999
Event Time: 04:35 [EDT]
Last Update Date: 08/14/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
HAROLD GRAY (R1)
HAROLD GRAY (R1)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 3 | N | Y | 95 | Power Operation | 95 | Power Operation |
HIGH PRESSURE COOLANT INJECTION (HPCI) SYSTEM DECLARED INOPERABLE DUE TO OSCILLATIONS IN PARAMETERS DISCOVERED DURING PLANNED TESTING.
"HPCI INOPERABLE DUE TO FLOW, PRESSURE AND SPEED OSCILLATIONS WHILE IN AUTOMATIC AND MANUAL. IT WAS DISCOVERED DURING PLANNED HPCI TESTING. TROUBLESHOOTING IS IN PROGRESS AND REPAIR PLANS ARE BEING MADE."
WITH THE HPCI SYSTEM INOPERABLE, UNIT 3 ENTERED THE 14 DAY LCO ACTION STATEMENT #99-3-625. THE LICENSEE PLANS TO INFORM THE NRC RESIDENT INSPECTOR.
"HPCI INOPERABLE DUE TO FLOW, PRESSURE AND SPEED OSCILLATIONS WHILE IN AUTOMATIC AND MANUAL. IT WAS DISCOVERED DURING PLANNED HPCI TESTING. TROUBLESHOOTING IS IN PROGRESS AND REPAIR PLANS ARE BEING MADE."
WITH THE HPCI SYSTEM INOPERABLE, UNIT 3 ENTERED THE 14 DAY LCO ACTION STATEMENT #99-3-625. THE LICENSEE PLANS TO INFORM THE NRC RESIDENT INSPECTOR.