35976
Power Reactor
Event Number: 35976
Facility: BRUNSWICK
Region: 2 State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: J. REINSBURROW
HQ OPS Officer: BOB STRANSKY
Region: 2 State: NC
Unit: [1] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: J. REINSBURROW
HQ OPS Officer: BOB STRANSKY
Notification Date: 07/31/1999
Notification Time: 15:22 [ET]
Event Date: 07/31/1999
Event Time: 11:41 [EDT]
Last Update Date: 07/31/1999
Notification Time: 15:22 [ET]
Event Date: 07/31/1999
Event Time: 11:41 [EDT]
Last Update Date: 07/31/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
ROBERT HAAG (R2)
ROBERT HAAG (R2)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
| 2 | N | Y | 100 | Power Operation | 100 | Power Operation |
CONTROL BUILDING VENTILATION ISOLATION
"On 7/31/99 at 11:41 during change out of the Brunswick site chlorine tank car an isolation of the control building ventilation system occurred. Two chlorine detectors actuated at the Service Water building adjacent to the chlorine tank car. These detectors isolate the control building ventilation system on detection of chlorine. The control building ventilation system components functioned as designed.
"The evolution in progress during the isolation was the disconnection of the spent chlorine tank car. Personnel in the area of the tank car with portable chlorine detection equipment did not detect the presence of chlorine gas. Subsequent inspections of areas adjacent to the tank car did not identify chlorine gas with portable monitors."
The chlorine detectors were reset, and the ventilation system was restored to its normal lineup. The NRC resident inspector has been informed of this event by the licensee.
"On 7/31/99 at 11:41 during change out of the Brunswick site chlorine tank car an isolation of the control building ventilation system occurred. Two chlorine detectors actuated at the Service Water building adjacent to the chlorine tank car. These detectors isolate the control building ventilation system on detection of chlorine. The control building ventilation system components functioned as designed.
"The evolution in progress during the isolation was the disconnection of the spent chlorine tank car. Personnel in the area of the tank car with portable chlorine detection equipment did not detect the presence of chlorine gas. Subsequent inspections of areas adjacent to the tank car did not identify chlorine gas with portable monitors."
The chlorine detectors were reset, and the ventilation system was restored to its normal lineup. The NRC resident inspector has been informed of this event by the licensee.