3596235963359653596636001

Power Reactor
Event Number: 35962
Facility: COOPER
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: WILLIAM B. GREEN
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/27/1999
Notification Time: 12:50 [ET]
Event Date: 07/27/1999
Event Time: 08:50 [CDT]
Last Update Date: 07/27/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
BILL JONES (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
INVALID HALF GROUP VII ISOLATION

AT 0850 CDT 07/27/99, AN INVALID HALF GROUP VII ISOLATION OCCURRED ON THE 'A" LOGIC. THIS ISOLATION IS NORMALLY CAUSED BY A LOW REACTOR WATER LEVEL SIGNAL, GREATER THAN OR EQUAL TO -113 INCHES, OR A HIGH MAIN STEAM LINE RADIATION SIGNAL, LESS THAN OR EQUAL TO 3 TIMES NORMAL FULL POWER BACKGROUND. NEITHER OF THESE SIGNALS WERE PRESENT. REACTOR RECIRCULATION AIR OPERATED VALVE #RR-AO-741, SAMPLE POINT 1 INBOARD ISOLATION VALVE, CLOSED AS A RESULT OF THIS CONDITION. THIS ISOLATION RESULTED IN THE PLANT ENTERING LCO 3.4.1, CONDITION "B", DUE TO THE INABILITY TO SAMPLE THE REACTOR COOLANT.

UNRELATED WORK WAS BEING PERFORMED IN THE GENERAL AREA OF THE ISOLATION RELAY. A SPURIOUS ACTUATION OF THE RELAY OCCURRED, RESULTING IN THE VALVE ISOLATION. AN INVESTIGATION OF THIS EVENT IS IN PROGRESS. THE RELAY WAS RESET WITH STATION PERSONNEL PRESENT TO DETERMINE THAT THE RELAY HAD FUNCTIONED PROPERLY. THE HALF GROUP ISOLATION HAS BEEN RESET AND VALVE #RR-AO-741 HAS BEEN REOPENED. LCO 3.4.1 HAS BEEN EXITED DUE TO THE SAMPLING FUNCTION BEING RETURNED TO SERVICE.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 35963
Facility: LIMERICK
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: PETE GARDNER
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/27/1999
Notification Time: 13:25 [ET]
Event Date: 07/27/1999
Event Time: 11:45 [EDT]
Last Update Date: 07/28/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
JOHN KINNEMAN (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
RESIDUAL HEAT REMOVAL (RHR) PUMP RECEIVED A START SIGNAL DURING A SURVEILLANCE TEST.

AT 1145 ON 07/27/99, DURING PERFORMANCE OF A SURVEILLANCE TEST FOR REMOTE SHUTDOWN PANEL OPERABILITY (ST-2-088-321-2), THE "2A" RHR PUMP RECEIVED A START SIGNAL. AT THE TIME, CONTROL OF THE PUMP HAD BEEN TRANSFERRED TO THE REMOTE SHUTDOWN PANEL. THE PUMP START WAS UNEXPECTED AND THUS, IS BEING REPORTED AS AN ESF ACTUATION UNDER THE GUIDANCE OF LIMERICK REPORTABILITY MANUAL (F-02). THE TRANSFER SWITCH WAS BEING CLEANED AND CYCLED DURING THE PUMP START AND AT THIS TIME IT IS BELIEVED THAT A CONTACT HAD INADVERTENTLY MADE UP. THE CAUSE OF THE EVENT IS BEING INVESTIGATED AND THE "2A" RHR PUMP AND THE REMOTE SHUTDOWN PANEL HAVE CONSERVATIVELY BEEN DECLARED INOPERABLE UNTIL THE INVESTIGATION IS COMPLETE. THE RHR PUMP WAS REMOVED FROM SERVICE AFTER RETURNING CONTROL POWER VIA THE REMOTE SHUTDOWN TRANSFER SWITCH.

ALL OTHER EMERGENCY CORE COOLING SYSTEMS ARE FULLY OPERABLE, IF NEEDED.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.


***RETRACTION ON 07/28/99 AT 1137 ET BY STAN T. GAMBLE TAKEN BY MACKINNON***

TECHNICAL SPECIFICATION SURVEILLANCE TESTING (ST-2-088-321-2) WAS BEING CONDUCTED AT THE REMOTE SHUTDOWN PANEL (RSP). A FLUKE 8050A MULTIMETER (DVM) WAS INSTALLED IN THE CONTROL CIRCUIT TO DETERMINE THE CONDITION OF HANDSWITCH CONTACTS. THE TEST DIRECTED PLACING THE CONTROL TRANSFER SWITCH IN THE "NORMAL" POSITION PRIOR TO REMOVING THE DVM FROM THE CIRCUIT. THE "2A" RHR PUMP 4KV BREAKER CLOSED WHEN THE TRANSFER SWITCH WAS MOVED FROM "EMERGENCY" TO "NORMAL" DUE TO THE DVM EFFECTIVELY JUMPERING THE CONTROL CIRCUIT PUMP START CONTACTS. THE "2A" RHR PUMP RAN ON MINIMUM FLOW FOR APPROXIMATELY FIFTEEN MINUTES WHILE INFORMATION WAS OBTAINED TO SUPPORT THE INVESTIGATION. THE PUMP WAS THEN SECURED BY MAIN CONTROL ROOM OPERATORS.

THE BASIS FOR THIS RETRACTION IS THAT A SINGLE COMPONENT ACTUATION OCCURRED IN A COMPLEX SYSTEM. THE RHR PUMP ALONE COULD NOT HAVE MITIGATED THE CONSEQUENCES OF A SIGNIFICANT EVENT. VALVE ALIGNMENT WOULD BE REQUIRED TO SUPPORT COMPLETION OF THE SAFETY FUNCTION. VALVE LOGIC WAS NOT AFFECTED BY THE DVM INSTALLATION. THEREFORE, THIS EVENT IS NOT REPORTABLE PER THE GUIDANCE OF NUREG-1022, REV. 1. R1DO (JOHN KINNEMAN) NOTIFIED.

THE NRC RESIDENT INSPECTOR WAS NOTIFIED OF THIS EVENT RETRACTION.


Power Reactor
Event Number: 35965
Facility: INDIAN POINT
Region: 1     State: NY
Unit: [] [3] []
RX Type: [2] W-4-LP,[3] W-4-LP
NRC Notified By: STEPHEN DAVIS
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/27/1999
Notification Time: 19:57 [ET]
Event Date: 07/27/1999
Event Time: 19:00 [EDT]
Last Update Date: 07/27/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
JOHN KINNEMAN (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
A MODIFIED CONNECTION BETWEEN TWO CONTAINMENT ISOLATION VALVES WAS FOUND TO LEAK WHICH PLACED UNIT 3 OUTSIDE ITS DESIGN BASIS.

DURING THE RETURN OF PIPING PENETRATIONS TO SERVICE FOLLOWING THE INSTALLATION OF A MODIFICATION TO THE ISOLATION VALVE SEAL WATER SYSTEM, IT WAS DETERMINED THAT A MODIFIED CONNECTION BETWEEN CONTAINMENT ISOLATION VALVES #WD-AOV-1723 AND #WD-AOV-1728 LEAKED. UPON INVESTIGATION, AT 1727, IT WAS DETERMINED THAT CONTAINMENT INTEGRITY WAS NOT ESTABLISHED. THE AFFECTED PENETRATIONS WERE ISOLATED AT 1810, BY DEACTIVATING INNER AIR OPERATED VALVES OR BY LOCKED CLOSED MANUAL VALVES. AT 1900, IT WAS DETERMINED THAT UNIT 3 HAD BEEN POTENTIALLY OUTSIDE ITS DESIGN BASIS BETWEEN 1610, WHEN THE PIPING PENETRATIONS WERE RETURNED TO SERVICE, AND 1810, WHEN THE PENETRATIONS WERE ISOLATED. DURING THE PERIOD WHEN THE PIPING PENETRATION WERE UNISOLATED, A POSTULATED SINGLE FAILURE COULD HAVE RESULTED IN A DIRECT PATHWAY FROM CONTAINMENT ATMOSPHERE TO PRIMARY AUXILIARY BUILDING ATMOSPHERE.

THE LICENSEE WILL INFORM THE NRC RESIDENT INSPECTOR.


Power Reactor
Event Number: 35966
Facility: COOK
Region: 3     State: MI
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: SAM PARTIN
HQ OPS Officer: JOHN MacKINNON
Notification Date: 07/27/1999
Notification Time: 21:10 [ET]
Event Date: 07/27/1999
Event Time: 18:45 [EDT]
Last Update Date: 07/27/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(i) - DEG/UNANALYZED COND
Person (Organization):
GEOFFREY WRIGHT (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
2 N N 0 Refueling 0 Refueling
Event Text
ALL FOUR EMERGENCY DIESEL GENERATORS (EDGs) DECLARED INOPERABLE BUT FUNCTIONAL..

DURING THE RECENT EXPANDED SYSTEM READINESS REVIEW, IT WAS IDENTIFIED THAT THE EDG COMBUSTION AIR INTAKE AND EXHAUST STRUCTURES AND THE EDG ROOM VENTILATION INTAKE AND EXHAUST STRUCTURES MAY NOT MEET THE DESIGN CRITERIA SPECIFIED IN THE UFSAR. IT IS APPARENT THAT THESE STRUCTURES MAY NOT BE CAPABLE OF WITHSTANDING THE EFFECTS OF TORNADO GENERATED MISSILES. THE LICENSEE CURRENTLY DOES NOT HAVE REASONABLE ASSURANCE THAT, WHILE THE REACTOR WAS IN OPERATION, THE EDGs WOULD HAVE PERFORMED THEIR SAFETY FUNCTION DURING A TORNADO EVENT.

FURTHER EVALUATIONS ARE IN PROCESS TO DETERMINE THE CORRECTIVE ACTIONS NEEDED TO RESTORE THE EDGs TO OPERABLE STATUS.

UNIT 1 IS IN MODE 5 AND UNIT 2 IS DEFUELED. ALL EDGs ARE FUNCTIONAL. THE LICENSEE IS PURSUING JUSTIFICATION TO ALLOW THE START OF OFFLOADING THE UNIT 1 CORE. BOTH UNITS HAVE BEEN SHUTDOWN SINCE 09/12/97.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.


Power Reactor
Event Number: 36001
Facility: WATERFORD
Region: 4     State: LA
Unit: [3] [] []
RX Type: [3] CE
NRC Notified By: ARTHUR E. WEMETT
HQ OPS Officer: LEIGH TROCINE
Notification Date: 08/06/1999
Notification Time: 13:37 [ET]
Event Date: 07/27/1999
Event Time: 08:12 [CDT]
Last Update Date: 08/06/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
TOM STETKA (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
3 N Y 100 Power Operation 100 Power Operation
Event Text
FIRE PROTECTION ISSUE

The following text is a portion of a facsimile received from the licensee:

"During evaluation of the design bases for the plant sprinkler systems and to revise the sprinkler system specifications, it was identified on July 27, 1999, that a fire area that contains essential cables was not in complete compliance with the requirements of 10 CFR Part 50, Appendix 'R.' The requirement is that safe shutdown equipment is located in an area where there is 1) fire detection and automatic fire suppression equipment installed in the area and 2) separation of at least 20 feet with no intervening combustibles or adequate fire barriers. It was determined [that] the sprinkler and detection systems did not provide coverage of the entire area. It was also determined [that] though the essential cables are separated by at least [20] feet, there are intervening combustibles and no rated fire barriers between the cables. Contingency actions (fire watches established in the effected zone) were implemented to address the non-conformance at the time of discovery. Upon further review by licensing personnel, it was determined to be reportable in accordance with 10CFR50.72."

The licensee notified the NRC resident inspector.