Power Reactor
Event Number: 35867
Facility: LIMERICK
Region: 1     State: PA
Unit: [] [2] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DOUGLAS AMTSFIELD
HQ OPS Officer: DOUG WEAVER
Notification Date: 06/26/1999
Notification Time: 05:28 [ET]
Event Date: 06/26/1999
Event Time: 04:03 [EDT]
Last Update Date: 07/23/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
GLENN MEYER (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
HIGH PRESSURE COOLANT INJECTION (HPCI) SYSTEM INOPERABLE

On 6-26-99 at 0403, the Unit 2 HPCI System was declared inoperable following performance of a routine test on the HPCI drain pot orifice. The purpose of the test is to verify flow through the HPCI turbine exhaust drain pot discharge line flow orifice. At the time of the failure the HPCI System was operable. The HPCI System was conservatively declared inoperable due to the potential for the exhaust line to fill.

The licensee notified the NRC Resident Inspector.

* * * UPDATE AT 1449 EDT ON 07/23/99 FROM STANLEY GAMBLE TO S. SANDIN * * *

The licensee is retracting this report based on the following:

The HPCI System was conservatively declared inoperable due to the potential for water to be present in the turbine as a result of a plugged flow orifice on the turbine exhaust drain pot drain line. The plugged orifice was discovered during performance of a test specifically designed to ensure that exhaust drain pot drain line flow path is operable. Testing is routinely scheduled the day following normal HPCI System surveillance testing since operation of the HPCI System is the initiator for plugging of the flow orifice.

The basis for this retraction is that a minimal amount, less than one gallon, of condensate was drained from the exhaust drain pot when the flow orifice piping was disassembled. The amount of condensate was much less than the amount required to adversely impact HPCI System operability. It would require in excess of 40 gallons of condensate to fill the exhaust drain pot to a level that would result in condensate entering the turbine or exhaust line. Therefore, the HPCI System was operable and capable of performing its safety function until it was removed from service to clear the flow orifice.

The licensee informed the NRC Resident Inspector.

The NRC Operations Officer notified R1DO (Jim Noggle).


Fuel Cycle Facility
Event Number: 35868
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: KURT SISLER
HQ OPS Officer: DOUG WEAVER
Notification Date: 06/26/1999
Notification Time: 10:44 [ET]
Event Date: 06/26/1999
Event Time: 08:30 [EDT]
Last Update Date: 06/26/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
MIKE JORDAN (R3)
Event Text
NOTIFICATION OF ANOTHER FEDERAL AGENCY

The licensee notified the DOE of an event in the X-705 building annex cylinder cleaning area. While attempting to clean an empty 8" cylinder it was discovered that the cylinder would not fit into the cadmium shield. It was later discovered that the NCSA had been based on a cylinder design which was slightly smaller than the older cylinder which caused the problem. A new NCSA will be performed.


Power Reactor
Event Number: 35869
Facility: THREE MILE ISLAND
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] B&W-L-LP,[2] B&W-L-LP
NRC Notified By: BLAIR
HQ OPS Officer: BOB STRANSKY
Notification Date: 06/26/1999
Notification Time: 13:18 [ET]
Event Date: 06/26/1999
Event Time: 10:08 [EDT]
Last Update Date: 06/26/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
KURT COWGILL (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
EDG STARTED AND LOADED DUE TO LOSS OF AUXILIARY TRANSFORMER

At 1008, the '1B' 230 kV auxiliary transformer failed for unknown reasons. The '1A' emergency diesel generator (EDG) automatically started and loaded to its associated 4kV emergency bus. The unit is currently stable at 100% power. The licensee stated that EDG will remain loaded to its emergency bus until the auxiliary transformer can be restored to service. The NRC resident inspector has been informed of this event by the licensee.


!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Fuel Cycle Facility
Event Number: 35871
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: DALE NOEL
HQ OPS Officer: BOB STRANSKY
Notification Date: 06/26/1999
Notification Time: 19:04 [ET]
Event Date: 06/26/1999
Event Time: 05:33 [EDT]
Last Update Date: 07/08/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
76.120(c)(2) - SAFETY EQUIPMENT FAILURE
Person (Organization):
MIKE JORDAN (R3)
ROBERT PIERSON (NMSS)
Event Text
MOTOR STOP BUTTON FAILED TO FUNCTION AS DESIGNED

"ON 6/26/99 AT 0533 HOURS, THE X-333 PROCESS BUILDING AREA CONTROL ROOM (ACR) #1 MOTOR STOP BUTTON FAILED TO FUNCTION AS DESIGNED WHEN CALLED UPON TO SHUTDOWN MOTORS ON CELL 33-5-10 (CASCADE OPERATIONAL MODE Ill). THIS REPRESENTS THE FAILURE OF TECHNICAL SAFETY REQUIREMENT (TSR) SURVEILLANCE 2.2.3.14.3 FOR CASCADE D.C. CONTROL POWER WHICH STATES: 'UTILIZE THE ACR MOTOR STOP BUTTON FOR EACH SCHEDULED CELL TRIP. MONITOR EXPECTED CELL BLOCK VALVE CLOSURE AND ANY RECYCLE VALVE ACTUATION.' OPERATIONS PERSONNEL IMMEDIATELY UTILIZED AN ALTERNATE MEANS LOCATED AT THE CELLS LOCAL CONTROL CENTER (LCC) TO TRIP CELL 33-5-10 MOTORS.

"THIS EVENT IS REPORTABLE DUE TO A SAFETY SYSTEM COMPONENT (SSC) REQUIRED BY THE TSR NOT BEING AVAILABLE OR OPERABLE AND NO REDUNDANT EQUIPMENT WAS AVAILABLE TO PERFORM THE REQUIRED SAFETY FUNCTION.

"THERE WAS NO LOSS OF HAZARDOUS/RADIOACTIVE MATERIAL OR RADIOACTIVE/RADIOLOGICAL CONTAMINATION EXPOSURE AS A RESULT OF THIS EVENT."

The NRC resident inspector has been informed of this event by the licensee.

* * * UPDATE AT 1820 ON 7/8/99 BY SISLER, RECEIVED BY WEAVER * * *

"THIS EVENT RETRACTION IS BEING SUBMITTED BASED ON FURTHER REVIEW OF THE PROCESS CELL DC CONTROL AND TRIP CIRCUITRY. TSR 2.2.3.14.3 SPECIFIES THAT DC CONTROL (CELL TRIP) POWER FOR UF6 STAGE MOTORS SHALL BE OPERABLE. AS PART OF THE CELL TRIP CIRCUIT THERE ARE FOUR REMOTE LOCATIONS FROM WHICH THE X-333 CELLS COULD BE TRIPPED (i.e., THE ACR, LCC, X-533 SWITCHYARD AND X-300). THE PURPOSE OF THE TSR SURVEILLANCE 2.2.3.14.3, WHICH REQUIRES THE USE OF THE ACR MOTOR STOP BUTTON DURING SCHEDULED CELL SHUTDOWNS, IS TO DEMONSTRATE THE RELIABILITY OF THE ACR CELL TRIP FUNCTION.

"HOWEVER, IN A TRANSIENT CONDITION, ANY OF THE CELL TRIP LOCATIONS MAY BE USED TO INITIATE CELL SHUTDOWN. IN THIS EVENT, THE CELL WAS BEING SHUTDOWN DUE TO A TRANSIENT CONDITION (SURGING) AND THE SURVEILLANCE REQUIREMENT DID NOT APPLY. THE CELL WAS SUCCESSFULLY SHUTDOWN UTILIZING THE LCC WHICH DEMONSTRATED THAT THE CELL TRIP CIRCUIT WAS OPERABLE.

"THIS EVENT IS BEING RETRACTED BASED UPON DC CONTROL AND CELL TRIP POWER WAS OPERABLE, LIMITING CONDITIONS FOR OPERATIONS (LCO) WAS MAINTAINED AND A SAFETY FAILURE DID NOT OCCUR."

The licensee notified the NRC resident Inspector. The operations center notified the R3DO (Vegel).