Event Notification Report for June 22, 1999
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
06/21/1999 - 06/22/1999
EVENT NUMBERS
35851
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
!!!!! THIS EVENT HAS BEEN RETRACTED !!!!!
Power Reactor
Event Number: 35851
Facility: WOLF CREEK
Region: 4 State: KS
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: FERGUSON
HQ OPS Officer: CHAUNCEY GOULD
Region: 4 State: KS
Unit: [1] [] []
RX Type: [1] W-4-LP
NRC Notified By: FERGUSON
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/22/1999
Notification Time: 18:23 [ET]
Event Date: 06/22/1999
Event Time: 16:48 [CDT]
Last Update Date: 07/07/1999
Notification Time: 18:23 [ET]
Event Date: 06/22/1999
Event Time: 16:48 [CDT]
Last Update Date: 07/07/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
10 CFR Section:
50.72(b)(1)(ii)(B) - OUTSIDE DESIGN BASIS
Person (Organization):
JOSEPH TAPIA (R4)
JOSEPH TAPIA (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | Y | 100 | Power Operation | 100 | Power Operation |
SEPARATION CRITERIA FOR REACTOR TRIP SWITCHGEAR NOT MET.
IT WAS DISCOVERED THAT BOTH TRAINS OF THE REACTOR TRIP SWITCHGEAR WERE 12" APART WHILE THE REQUIRED SEPARATION IS 20 FEET. THIS CONDITION PUTS THE PLANT OUTSIDE ITS DESIGN BASIS AS PER 10CFR50 APPENDIX R, SEC. III.G.2. THEY HAVE STATIONED A CONTINUOUS FIRE WATCH IN THE AREA. PLANT OPERATION WILL CONTINUE. AS A CORRECTIVE MEASURE VARIOUS OPTIONS ARE BEING CONSIDERED, WITH ONE REQUIRING A PLANT SHUTDOWN. THEY HAVE NOT YET DETERMINED WHICH CORRECTIVE OPTION THEY WILL IMPLEMENT. INSTRUCTIONS HAVE BEEN GIVEN TO TRIP THE REACTOR UPON A REPORT FROM THE CONTINUOUS FIRE WATCH OF AN ACTIVE FIRE IN THE AREA THAT IS BEING MONITORED.
THE RESIDENT INSPECTOR WAS NOTIFIED.
***RETRACTION ON 07/07/99 AT 1721 ET BY D. DEES TAKEN BY MACKINNON***
BASED ON ENGINEERING EVALUATION THE PLANT WAS NOT OUTSIDE ITS DESIGN BASIS WITH RESPECT TO APPENDIX "R" TO 10CFR50. THE APPROVED FIRE PROTECTION PROGRAM ALLOWS A DIVERSE MEANS TO ACHIEVE SAFE SHUTDOWN, AS IDENTIFIED IN WCGS RESPONSE TO APPENDIX "R" SECTION III.G. IN THIS CASE, THE DIVERSE MEANS TO ACHIEVE AND MAINTAIN SAFE SHUTDOWN USING EQUIPMENT FREE OF FIRE DAMAGE IS ACCOMPLISHED THROUGH MANUAL ROD INSERTION AS SPECIFIED IN EMG FR-S1, RESPONSE TO NUCLEAR POWER GENERATION/ATWT. THEREFORE, THIS EVENT IS BEING RETRACTED. R4DO (CHARLES MARSCHALL) NOTIFIED.
THE NRC RESIDENT INSPECTOR WILL BE NOTIFIED OF THIS RETRACTION BY THE LICENSEE.
IT WAS DISCOVERED THAT BOTH TRAINS OF THE REACTOR TRIP SWITCHGEAR WERE 12" APART WHILE THE REQUIRED SEPARATION IS 20 FEET. THIS CONDITION PUTS THE PLANT OUTSIDE ITS DESIGN BASIS AS PER 10CFR50 APPENDIX R, SEC. III.G.2. THEY HAVE STATIONED A CONTINUOUS FIRE WATCH IN THE AREA. PLANT OPERATION WILL CONTINUE. AS A CORRECTIVE MEASURE VARIOUS OPTIONS ARE BEING CONSIDERED, WITH ONE REQUIRING A PLANT SHUTDOWN. THEY HAVE NOT YET DETERMINED WHICH CORRECTIVE OPTION THEY WILL IMPLEMENT. INSTRUCTIONS HAVE BEEN GIVEN TO TRIP THE REACTOR UPON A REPORT FROM THE CONTINUOUS FIRE WATCH OF AN ACTIVE FIRE IN THE AREA THAT IS BEING MONITORED.
THE RESIDENT INSPECTOR WAS NOTIFIED.
***RETRACTION ON 07/07/99 AT 1721 ET BY D. DEES TAKEN BY MACKINNON***
BASED ON ENGINEERING EVALUATION THE PLANT WAS NOT OUTSIDE ITS DESIGN BASIS WITH RESPECT TO APPENDIX "R" TO 10CFR50. THE APPROVED FIRE PROTECTION PROGRAM ALLOWS A DIVERSE MEANS TO ACHIEVE SAFE SHUTDOWN, AS IDENTIFIED IN WCGS RESPONSE TO APPENDIX "R" SECTION III.G. IN THIS CASE, THE DIVERSE MEANS TO ACHIEVE AND MAINTAIN SAFE SHUTDOWN USING EQUIPMENT FREE OF FIRE DAMAGE IS ACCOMPLISHED THROUGH MANUAL ROD INSERTION AS SPECIFIED IN EMG FR-S1, RESPONSE TO NUCLEAR POWER GENERATION/ATWT. THEREFORE, THIS EVENT IS BEING RETRACTED. R4DO (CHARLES MARSCHALL) NOTIFIED.
THE NRC RESIDENT INSPECTOR WILL BE NOTIFIED OF THIS RETRACTION BY THE LICENSEE.