Skip to main content

Event Notification Report for June 11, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
06/10/1999 - 06/11/1999

EVENT NUMBERS
3581435815

Fuel Cycle Facility
Event Number: 35814
Facility: PORTSMOUTH GASEOUS DIFFUSION PLANT
Region: 3     State: OH
Unit: [] [] []
RX Type: URANIUM ENRICHMENT FACILITY
Comments: 2 DEMOCRACY CENTER
6903 ROCKLEDGE DRIVE
BETHESDA, MD 20817 (301)564-3200
NRC Notified By: SPAETH
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/11/1999
Notification Time: 17:42 [ET]
Event Date: 06/11/1999
Event Time: 13:45 [EDT]
Last Update Date: 06/11/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
BRUCE JORGENSEN (R3)
TED SHERR (NMSS)
FRANK CONGEL (IRO)
Event Text
4 HOUR 91-01 BULLETIN

THE SITE REPORTED THAT AT 1345, OPERATIONS PERSONNEL DISCOVERED STANDING WATER UNDER AUTOCLAVE #6 IN THE X-343, FEED AND SAMPLING FACILITY. STANDING WATER IS AN INDICATION THAT A DRAIN UNDER THE AUTOCLAVE WAS PLUGGED. THE PLUGGED DRAIN IS NOT THE AUTOCLAVE DRAIN, BUT THE CONTAINMENT PIT UNDER THE AUTOCLAVE. THIS CONDITION IS ANALYZED IN THE NUCLEAR CRITICALITY SAFETY EVALUATION, NCSE-0343_002.001 CONTINGENCY EVENT 6.3a, WHICH STATES IN PART, "THE AUTOCLAVES ARE MOUNTED INSIDE LARGE CONCRETE PITS, WHICH ARE NORMALLY DRY AND ARE PREVENTED FROM ACCUMULATING WATER FROM ANY SOURCE BY A 4 INCH DRAIN."

THE NUCLEAR CRITICALITY SAFETY (NCS) STAFF DETERMINED THAT A NUCLEAR CRITICALITY SAFETY APPROVAL FOR THIS OPERATION WAS DEFICIENT IN THAT IT FAILED TO IDENTIFY THE CONTROLS NECESSARY TO MAINTAIN THE ANALYZED CONDITION. BUILDING AND NCS PERSONNEL HAVE DETERMINED THAT NO OTHER SIMILAR CONDITIONS EXISTS.

SAFETY SIGNIFICANCE IS LOW, THERE ARE NO CREDIBLE PATHWAYS TO CRITICALITY AND THERE IS NO URANIUM IN THE PIT.

MEASURES WERE PUT IN PLACE TO REGAIN COMPLIANCE AND ADMINISTRATIVE CONTROLS IMPLEMENTED TO ASSURE COMPLIANCE IS MAINTAINED IN THE FUTURE.

THE NRC RESIDENT INSPECTOR WILL BE INFORMED ALONG WITH THE DOE REPRESENTATIVE.


Power Reactor
Event Number: 35815
Facility: LIMERICK
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] GE-4,[2] GE-4
NRC Notified By: DOUGHDRTY
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 06/11/1999
Notification Time: 22:50 [ET]
Event Date: 06/11/1999
Event Time: 19:20 [EDT]
Last Update Date: 06/11/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
CURTIS COWGILL (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
PLANT HAD A REACTOR SCRAM FROM 100% POWER DUE TO PERSONNEL ERROR.

THE UNIT 1 REACTOR SCRAMMED ON A "TURBINE CONTROL VALVE FAST CLOSURE" RPS SIGNAL DURING THE PERFORMANCE OF THE "BACKUP OVERSPEED AND POWER LOAD UNBALANCE TEST".
THE CAUSE OF THE SCRAM WAS OPERATOR ERROR. THE FOLLOWING ESF ISOLATIONS OCCURRED ON A VALID WIDE RANGE LEVEL "2" OF -38 INCHES: REACTOR WATER CLEANUP, REACTOR ENCLOSURE SECONDARY CONTAINMENT HVAC, AND CONTAINMENT LEAK DETECTION. ALL ISOLATIONS HAVE BEEN RESET. ALL RODS FULLY INSERTED, NO INJECTION OCCURRED AND NO SAFETY/RELIEF VALVES LIFTED. THE HEAT SINK IS THE MAIN CONDENSER.

THE RESIDENT INSPECTOR WAS NOTIFIED.