Skip to main content

Event Notification Report for May 27, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
05/26/1999 - 05/27/1999

EVENT NUMBERS
3577335771

Power Reactor
Event Number: 35773
Facility: SOUTH TEXAS
Region: 4     State: TX
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: MIKE SCHAEFER
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 05/27/1999
Notification Time: 15:33 [ET]
Event Date: 05/27/1999
Event Time: 13:45 [CDT]
Last Update Date: 05/27/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
73.71(b)(1) - SAFEGUARDS REPORTS
Person (Organization):
THOMAS ANDREWS (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
- PHYSICAL SECURITY REPORT -

DISCOVERY OF CRIMINAL INFORMATION INVOLVING A CONTRACTOR WHO WAS GRANTED UNESCORTED ACCESS TO THE PLANT. COMPENSATORY MEASURES WERE IMMEDIATELY TAKEN UPON DISCOVERY. THE LICENSEE PLANS TO INFORM THE NRC RESIDENT INSPECTOR. REFER TO THE NRC OPERATIONS OFFICER LOG FOR ADDITIONAL DETAILS.


Power Reactor
Event Number: 35771
Facility: FARLEY
Region: 2     State: AL
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: VAUDY HOLLEY
HQ OPS Officer: JOHN MacKINNON
Notification Date: 05/27/1999
Notification Time: 11:06 [ET]
Event Date: 05/27/1999
Event Time: 08:56 [CDT]
Last Update Date: 05/27/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
Person (Organization):
THOMAS DECKER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 A/R Y 100 Power Operation 0 Hot Standby
Event Text
AUTOMATIC REACTOR TRIP ON 2 OUT OF 3 OVERTEMPERATURE DELTA-TEMPERATURE (OTdT). ALL RODS FULLY INSERTED INTO THE CORE.

At 0854 CDT while swapping Main Feedwater Pump "1A" Main Feedwater Pump lube oil coolers "1A" Main Feedwater Pump (MFW P "1A")tripped on low lube oil pressure. Operators manually ramped back the Main Turbine to reduce reactor power due to the loss of MFW P "1A". The Manual Main Turbine runback caused both Pressurizer PORVs valves to open/close (open a few seconds) when reactor coolant pressure increased to 2310 psig. The reactor tripped on a 2 out of 3 Overtemperature Delta-Temperature trip signal at 0856 CDT (Manual Main Turbine reduction in power was faster than the control rods reduction in reactor power). All rods fully inserted into the core. Both Motor Driven Auxiliary Feedwater Pumps started due to low Steam Generator Water Levels (caused by the Main Turbine runback and the automatic reactor trip). Currently Steam Generator Water Levels are being maintained by the operating Motor Driven Auxiliary Feedwater pumps. No Code Safety valves on the Primary or the Secondary side of the plant opened. No Steam Generator Atmospheric Valves opened. Reactor Power level was between 77% to 82% (Main Generator Power was at approximately 500 Mwe ) when the automatic reactor trip occurred. The licensee initially entered EEP-0 (Safety Injection/Reactor Trip procedure) performed the first 4 steps then entered ESP-0.1 (Reactor Trip Response procedure) and after completing ESP-0.1 they entered Unit Operating Procedure.
All Emergency Core Cooling Systems, Emergency Diesel Generators are available, if needed. Offsite electrical power is stable.

The licensee is investigating why Main Feedwater Pump "1A" tripped on low lube oil pressure.

The NRC Resident Inspector was notified of this event by the licensee.

***Update on 5/27/99 at 1352 EDT by Vaudy Holley taken by MacKinnon****

When the Pressurizer PORVs were opened it caused a reduction in the reactor pressure to drop low enough for the Overtemperature Delta-Temperature setpoints to be reached. This caused a reactor trip/turbine trip.
R2DO (Tom Decker) notified. The NRC Resident Inspector was notified.