357553575635757

Power Reactor
Event Number: 35755
Facility: BRAIDWOOD
Region: 3     State: IL
Unit: [1] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: DENNIS HIGINBOLHAM
HQ OPS Officer: FANGIE JONES
Notification Date: 05/22/1999
Notification Time: 05:10 [ET]
Event Date: 05/22/1999
Event Time: 03:15 [CDT]
Last Update Date: 05/22/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(1)(v) - OTHER ASMT/COMM INOP
Person (Organization):
BRENT CLAYTON (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
2 N Y 60 Power Operation 60 Power Operation
Event Text
PROCESS COMPUTER OUT-OF-SERVICE FOR PLANNED MAINTENANCE

The Plant Process Computer was placed out-of-service for modification to a inverter power supply and temporary power was not available. This also placed the Safety Parameter Display System (SPDS) and the ability to link to the Emergency Response Data System (ERDS) out-of-service.

Preparations for full restoration is in progress and it is expected to be complete by 0600 CDT.

The licensee plans to notify the NRC Resident Inspector.


Power Reactor
Event Number: 35756
Facility: COMANCHE PEAK
Region: 4     State: TX
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: GREGORY BRYAN
HQ OPS Officer: FANGIE JONES
Notification Date: 05/22/1999
Notification Time: 09:40 [ET]
Event Date: 05/22/1999
Event Time: 07:15 [CDT]
Last Update Date: 05/22/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
GARY SANBORN (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 N Y 100 Power Operation 100 Power Operation
Event Text
THE 'A' SAFEGUARDS BUS DEENERGIZED CAUSING THE DIESEL GENERATOR TO START AND REENERGIZE IT

The Train 'A' Safeguards 6.9 kV electrical bus experienced a lockout relay actuation (due to a neutral ground overcurrent). The diesel generator (2-01) started and energized the bus. The Blackout Sequencer actuated and restored the safeguards equipment on the affected bus. The ESF equipment that actuated included the 'A' Train Control Room HVAC, motor driven Auxiliary Feedwater Pump, turbine driven Auxiliary Feedwater Pump ( 'A' Train only), and the Blackout Sequencer.

The unit entered the abnormal procedure to respond to the loss of the normal power supply to the Train 'A' Bus and restore from the Blackout Sequencer.

The cause of the relay actuation is under investigation and the diesel generator will continue to power the bus until it is determined what caused the actuation.

The licensee notified the NRC Resident Inspector.


General Information or Other
Event Number: 35757
Rep Org: MEAD PAPER CORPORATION
Licensee: MEAD PAPER CORPORATION
Region: 3
City: CHILLICOTHE   State: OH
County:
License #: 34-06188-09
Agreement: N
Docket:
NRC Notified By: JIM SEGELHORST, RSO
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 05/22/1999
Notification Time: 12:01 [ET]
Event Date: 05/22/1999
Event Time: 07:10 [EDT]
Last Update Date: 05/22/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
Person (Organization):
BRENT CLAYTON (R3)
CHARLEY HAUGHNEY (NMSS)
Event Text
- OHMART DENSITY GAUGE (20 MILLICURIES Cs-137 SOURCE) IN A FIRE AT A PAPER PLANT -

AT 0710 ON 05/22/99, A FIRE OCCURRED IN A WOOD CHIP CONVEYOR, POSSIBLY DUE TO A SEIZED BEARING, AT THE MEAD PAPER CORPORATION FACILITY IN CHILLICOTHE, OH. THE LOCAL FIRE DEPARTMENT WAS CALLED AND RESPONDED TO THE FIRE, WHICH WAS EXTINGUISHED WITHIN APPROXIMATELY 15 MINUTES. A OHMART DENSITY GAUGE(MODEL #SH1-00PS), WHICH IS INSTALLED IN THE AREA OF THE FIRE, HAD ITS OUTER CASE CHARRED AND SLIGHTLY DAMAGED. THE GAUGE, WHICH CONTAINS A 20 MILLICURIE CESIUM-137 RADIATION SOURCE, APPEARS NOT TO BE DAMAGED.

JIM SEGELHORST, MEAD PAPER CORPORATION RADIATION SAFETY OFFICER (RSO) MEASURED THE SOURCE AND OBTAINED NORMAL READINGS AT A DISTANCE OF APPROXIMATELY ONE FOOT. THE RSO BARRICADED THE AREA AROUND THE GAUGE TO ISOLATE IT FROM PERSONNEL. A OHMART REPRESENTATIVE IS ON HIS WAY TO THE SITE AND PLANS TO TAKE POSSESSION OF THE GAUGE AROUND 1500 AND SHIP IT BACK TO THE MANUFACTURER. NO PERSONNEL WERE EXPOSED TO RADIATION.