Power Reactor
Event Number: 35591
Facility: COOPER
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] GE-4
NRC Notified By: FRED SCHIZAS
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 04/14/1999
Notification Time: 04:32 [ET]
Event Date: 04/14/1999
Event Time: 01:28 [CDT]
Last Update Date: 05/06/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
LINDA SMITH (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
- RCIC SYSTEM DECLARED INOPERABLE DUE TO FAILED SYSTEM COOLING VALVE DURING A TEST -

AT 0128 CDT ON 04/14/99, THE LICENSEE DECLARED THE REACTOR CORE ISOLATION COOLING (RCIC) SYSTEM INOPERABLE DUE TO THE FAILURE OF THE RCIC SYSTEM COOLING VALVE, #RCIC-MO-132. WHEN THE VALVE CONTROL SWITCH WAS PLACED IN THE CLOSE POSITION IN ORDER TO RECORD THE VALVE STROKE TIME DURING THE RCIC POWER-OPERATED VALVE OPERABILITY SURVEILLANCE TEST, THE VALVE MOVED TO THE INTERMEDIATE POSITION AND STOPPED. STATION OPERATORS VERIFIED THAT THE VALVE WAS NOT CLOSED AND ISOLATED THE RCIC SYSTEM STEAM SUPPLY AND SUCTION AND DISCHARGE PATHS IN ORDER TO PREVENT SYSTEM INITIATION, EVIDENCE PRESERVATION, AND EXCESSIVE CYCLING OF THE BAROMETRIC CONDENSER PUMP. STATION OPERATORS ALSO VERIFIED THAT THE HIGH PRESSURE COOLANT INJECTION SYSTEM WAS OPERABLE.

TECH SPEC LCO A/S 3.5.3.A REQUIRES THE LICENSE TO RESTORE THE RCIC SYSTEM TO OPERABLE STATUS WITHIN 14 DAYS OR SHUT THE PLANT DOWN.

STATION OPERATORS ARE INVESTIGATING THE CAUSE OF THE VALVE FAILURE AND PLAN TO REPAIR THE VALVE.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.

*** UPDATE ON 5/6/99 @ 1444 FROM SCHIZAS TO GOULD *** RETRACTION

OPERATION OF THE RCIC SYSTEM REQUIRES THE "RCIC-MOV-MO132" VALVE TO REMAIN OPEN. IT WAS DISCOVERED THAT THE FAILURE OF THIS VALVE WAS FOUND TO BE IN THE CLOSING STROKE POSITION ONLY. THIS VALVE WAS STROKED OPEN SUCCESSFULLY PRIOR TO AND DURING TROUBLESHOOTING. SINCE THE VALVE WAS ALMOST OPEN WHEN IT FAILED, IT IS CONCLUDED THAT THE RCIC SYSTEM COULD HAVE PERFORMED ITS SAFETY FUNCTION AND WAS NOT AFFECTED BY THE MALFUNCTION OF THE "RCIC-MOV-MO132" VALVE DURING THE CLOSING STROKE. THEREFORE, THIS EVENT IS NOT REPORTABLE AND IS BEING RETRACTED.

THE RESIDENT INSPECTOR WILL BE NOTIFIED.

REG 4 RDO(JONES) WAS NOTIFIED.


Power Reactor
Event Number: 35592
Facility: BRAIDWOOD
Region: 3     State: IL
Unit: [] [2] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: PAT HABEL
HQ OPS Officer: DICK JOLLIFFE
Notification Date: 04/14/1999
Notification Time: 06:50 [ET]
Event Date: 04/14/1999
Event Time: 04:33 [CDT]
Last Update Date: 04/15/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
JOHN JACOBSON (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
2 A/R Y 85 Power Operation 0 Hot Standby
Event Text
- AUTO Rx TRIP FROM 85% POWER DUE TO MAIN GENERATOR FAULT FOR UNKNOWN REASONS -

AT 0433 CDT ON 04/14/99, UNIT 2 AUTOMATICALLY TRIPPED FROM 85% POWER DUE TO A MAIN GENERATOR TRIP CAUSED BY A MAIN GENERATOR FAULT FOR UNKNOWN REASONS. ALL CONTROL RODS INSERTED COMPLETELY. BOTH TRAINS OF THE AUXILIARY FEEDWATER SYSTEM ACTUATED TO RESTORE STEAM GENERATOR WATER LEVELS TO NORMAL. NO SAFETY OR RELIEF VALVES LIFTED. STEAM IS BEING DUMPED TO THE MAIN CONDENSER. ALL SYSTEMS FUNCTIONED AS DESIGNED.

UNIT 2 IS STABLE IN MODE 3 (HOT STANDBY). THE LICENSEE IS INVESTIGATING THE CAUSE OF THE MAIN GENERATOR FAULT.

THE LICENSEE INFORMED THE NRC RESIDENT INSPECTOR.

* * * UPDATE AT 0408 ON 04/15/99 BY JOLLIFFE * * *

THE AUTOMATIC REACTOR TRIP WAS CAUSED BY A PROBLEM WITH A MAIN GENERATOR GIX GROUND FAULT RELAY. THE LICENSEE HAS BYPASSED THE RELAY AND RESTARTED UNIT 2. THE LICENSEE IS CONTINUING TO INVESTIGATE THE ROOT CAUSE OF THE REACTOR TRIP.


Power Reactor
Event Number: 35594
Facility: FT CALHOUN
Region: 4     State: NE
Unit: [1] [] []
RX Type: [1] CE
NRC Notified By: CHRISTENSEN
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 04/14/1999
Notification Time: 18:40 [ET]
Event Date: 04/14/1999
Event Time: 16:52 [CDT]
Last Update Date: 04/14/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(vi) - OFFSITE NOTIFICATION
Person (Organization):
LINDA SMITH (R4)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
THE LICENSEE NOTIFIED THE NEBRASKA STATE ENVIRONMENTAL AGENCY THAT THEY EXCEEDED THEIR NPDES DISCHARGE LIMITS FOR HYDRAZINE.

THE HYDRAZINE DISCHARGE AT OUTFALL 001 (CIRCULATING WATER DISCHARGE) WAS IN EXCESS OF THEIR NPDES (NATIONAL POLLUTANT DISCHARGE ELIMINATION SYSTEM) DISCHARGE LIMIT OF 2 PPB. THE MEASURED DISCHARGE RATE AT THE OUTFALL WAS 3 PPB, BUT THERE WAS NO NET INCREASE IN HYDRAZINE DISCHARGE CONCENTRATION FROM THE SITE SINCE UPSTREAM RIVER CONCENTRATION IS ALSO 3 PPB.

THE RESIDENT INSPECTOR WAS NOTIFIED.

HOO NOTE: SEE SIMILAR EVENTS #35524 AND #35542.