Event Number: 35590
Facility: GINNA
Region: 1     State: NY
Unit: [1] [] []
RX Type: [1] W-2-LP
NRC Notified By: GOMEZ
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 04/13/1999
Notification Time: 17:58 [ET]
Event Date: 04/13/1999
Event Time: 15:25 [EDT]
Last Update Date: 04/13/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
DAN HOLODY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N N 0 Cold Shutdown 0 Cold Shutdown
Event Text
PLANT HAD AUTO START AND LOADING OF THE EMERGENCY DIESEL "B".

THE PLANT IS IN MODE 5 FOR A REFUELING OUTAGE AND PERSONNEL WERE PERFORMING A SAFETY INJECTION FUNCTIONAL TEST. THIS TEST REQUIRES THE EMERGENCY DIESEL "B" TO BE PLACED IN LOCKOUT WHILE DEENERGIZING THE SAFEGUARDS BUSES. UPON COMPLETION OF THIS PORTION OF THE TEST, BUS RESTORATION WAS INITIATED. THE RESTORATION STEPS REQUIRE CLOSURE OF BUS 17 (SCREENHOUSE SAFEGUARDS BUS) NORMAL FEEDER BREAKER, BUT IT WOULD NOT CLOSE. RESTORATION CONTINUED WHILE TROUBLESHOOTING THE BUS 17 NORMAL FEEDER BREAKER PROBLEM. WHEN THE STEPS FOR DIESEL GENERATOR "B" WERE PERFORMED, THE DIESEL WAS RESET. UPON RESET, THE DIESEL GENERATOR "B" SAW THE UNDERVOLTAGE ON BUS 17, AUTO STARTED AND LOADED BUS 17 AS DESIGNED. THE DIESEL GENERATOR "B" WAS SECURED AT 1631 AND BUS 17 HAS BEEN REENERGIZED FROM NORMAL POWER SUPPLY. INITIAL INVESTIGATION SHOWED CAUSE OF THE FAILURE OF THE FEEDER BREAKER TO CLOSE WAS DUE TO A BLOWN UNDERVOLTAGE FUSE.

THE RESIDENT INSPECTOR WAS NOTIFIED.


Power Reactor
Event Number: 35587
Facility: NORTH ANNA
Region: 2     State: VA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: CROSSMAN
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 04/13/1999
Notification Time: 13:05 [ET]
Event Date: 04/13/1999
Event Time: 10:25 [EDT]
Last Update Date: 04/13/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(iii)(D) - ACCIDENT MITIGATION
Person (Organization):
PIERCE SKINNER (R2)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
THE CONTROL ROOM EMERGENCY VENTILATION FAN SUCTION SUPPLY DAMPER SWITCH FOUND IN THE INCORRECT POSITION.

THE CONTROL ROOM EMERGENCY FAN, "1-HV-F-42", SUCTION SUPPLY DAMPER SWITCH WAS FOUND IN THE "NORMAL MODE" POSITION INSTEAD OF THE "LOCKOUT" POSITION. THE SWITCH HAS TO BE IN THE "LOCKOUT" POSITION TO MAINTAIN THE CONTROL ROOM PRESSURE ENVELOPE IN THE RECIRCULATION MODE DURING THE INITIAL STAGES OF A FUEL HANDLING ACCIDENT OR SAFETY INJECTION. BY THE SWITCH BEING IN THE INCORRECT POSITION(NORMAL MODE) IT WOULD HAVE AFFECTED THE ABILITY OF THE FAN TO PERFORM ITS ACCIDENT FUNCTION. THE PLANT ENTERED A 7 DAY LCO UNDER TS 3.7.7.1 WHICH REQUIRES CORRECTIVE MEASURES TO BE IMPLEMENTED. THE SWITCH WAS PLACED IN THE CORRECT, "LOCKOUT", POSITION AT 10:32 AM. INVESTIGATION ON HOW THE SWITCH GOT INTO THE INCORRECT POSITION IS ONGOING.

THE RESIDENT INSPECTOR WAS NOTIFIED.


Power Reactor
Event Number: 35586
Facility: BEAVER VALLEY
Region: 1     State: PA
Unit: [1] [] []
RX Type: [1] W-3-LP,[2] W-3-LP
NRC Notified By: CHRIS HYNES
HQ OPS Officer: FANGIE JONES
Notification Date: 04/13/1999
Notification Time: 05:55 [ET]
Event Date: 04/13/1999
Event Time: 04:27 [EDT]
Last Update Date: 04/13/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
Person (Organization):
DAN HOLODY (R1)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R N 0 Hot Standby 0 Hot Standby
Event Text
MANUAL REACTOR TRIP DUE TO ROD CONTROL URGENT FAILURE ALARM

During a planned plant shutdown, with the reactor already subcritical, control bank 'A' group 2 did not move as rods were being inserted. As a result, the rod control system received an "Urgent Alarm" which inhibited manual control rod motion. The licensee performed a manual trip and all rods fully inserted. The problem is being investigated.

Heat removal was and is by steam dump to the main condenser with feedwater from the main feedwater system.

The licensee notified the NRC Resident Inspector.