Event Notification Report for April 10, 1999
U.S. Nuclear Regulatory Commission
Operations Center
EVENT REPORTS FOR
04/09/1999 - 04/10/1999
EVENT NUMBERS
35572
Power Reactor
Event Number: 35572
Facility: RIVER BEND
Region: 4 State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: HUSTON
HQ OPS Officer: FANGIE JONES
Region: 4 State: LA
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: HUSTON
HQ OPS Officer: FANGIE JONES
Notification Date: 04/10/1999
Notification Time: 07:46 [ET]
Event Date: 04/10/1999
Event Time: 03:10 [CDT]
Last Update Date: 04/10/1999
Notification Time: 07:46 [ET]
Event Date: 04/10/1999
Event Time: 03:10 [CDT]
Last Update Date: 04/10/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
10 CFR Section:
50.72(b)(2)(ii) - ESF ACTUATION
Person (Organization):
LAWRENCE YANDELL (R4)
LAWRENCE YANDELL (R4)
| Unit | SCRAM Code | RX Crit | Initial PWR | Initial RX Mode | Current PWR | Current RX Mode |
|---|---|---|---|---|---|---|
| 1 | N | N | 0 | Refueling | 0 | Refueling |
ESF SIGNAL INITIATED CAUSING SOME CONTAINMENT ISOLATION VALVES TO CLOSE
"While performing preparations for an ENS-SWG1A bus outage the alternate supply breaker ENS-ACB04 tripped. The bus was being supplied by this source and the resultant loss of power and invalid actuation signal caused several containment isolation AOVs to close. The containment purge system was in operation and isolated as designed. Two drain system valves (DFR-AOV102 and DER AOV127) and one sample system valve (B33-FO20) also isolated."
The trip took place during a clearance procedure when an individual, in the field, opened a fuse cabinet. The incident is being investigated. A limited restoration of systems has been done.
The licensee notified the NRC Resident Inspector.
"While performing preparations for an ENS-SWG1A bus outage the alternate supply breaker ENS-ACB04 tripped. The bus was being supplied by this source and the resultant loss of power and invalid actuation signal caused several containment isolation AOVs to close. The containment purge system was in operation and isolated as designed. Two drain system valves (DFR-AOV102 and DER AOV127) and one sample system valve (B33-FO20) also isolated."
The trip took place during a clearance procedure when an individual, in the field, opened a fuse cabinet. The incident is being investigated. A limited restoration of systems has been done.
The licensee notified the NRC Resident Inspector.