Skip to main content

Event Notification Report for January 18, 1999

U.S. Nuclear Regulatory Commission
Operations Center

EVENT REPORTS FOR
01/17/1999 - 01/18/1999

EVENT NUMBERS
3528035277

Power Reactor
Event Number: 35280
Facility: BRAIDWOOD
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] W-4-LP,[2] W-4-LP
NRC Notified By: CARL MOORE
HQ OPS Officer: DOUG WEAVER
Notification Date: 01/18/1999
Notification Time: 21:46 [ET]
Event Date: 01/18/1999
Event Time: 20:17 [CST]
Last Update Date: 01/19/1999
Emergency Class: UNUSUAL EVENT
10 CFR Section:
50.72(a)(1)(i) - EMERGENCY DECLARED
Person (Organization):
JIM GAVULA (R3)
BRUCE BOGER (NRR)
FRANK CONGEL (IRD)
SULLIVAN (FEMA)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 N Y 100 Power Operation 100 Power Operation
Event Text
UNUSUAL EVENT - LOSS OF APPROXIMATELY 50% OF CONTROL ROOM ANNUNCIATORS

"Loss of redundant Annunciator Power Supplies has rendered a substantial number of safety related annunciators inoperable. This required a GSEP notification - Unusual Event, (MU-6 - Loss of Annunciators for >= 15 minutes). Backup indications are available and increased main control board monitoring has been implemented."

The licensee has called in additional personnel to help with the increased monitoring. Troubleshooting on the power supplies is in progress. The NRC resident inspector has been notified.


*** UPDATE ON 01/19/99 @ 0539 BY RAUSH TO GOULD ***

THE PLANT TERMINATED THE NOUE AT 0407 WHEN TESTING VERIFIED THE SYSTEMS WERE FULLY OPERATIONAL. THE CAUSE OF THE POWER SUPPLY FAILURE WAS DUE TO A GROUND WHICH HAS BEEN REPAIRED. BOTH BACKUP AND MAIN POWER SUPPLY HAVE BEEN RETURNED TO SERVICE.

THE NRC RESIDENT INSPECTOR AND THE STATE WAS NOTIFIED.

THE REG 3 RDO(GAVULA) AND THE EO( BOGER )WERE NOTIFIED ALONG WITH FEMA (WRIGHT).


Power Reactor
Event Number: 35277
Facility: CLINTON
Region: 3     State: IL
Unit: [1] [] []
RX Type: [1] GE-6
NRC Notified By: FUNKHOUSER
HQ OPS Officer: CHAUNCEY GOULD
Notification Date: 01/18/1999
Notification Time: 09:26 [ET]
Event Date: 01/18/1999
Event Time: 04:41 [CST]
Last Update Date: 01/18/1999
Emergency Class: NON EMERGENCY
10 CFR Section:
50.72(b)(2)(ii) - RPS ACTUATION
Person (Organization):
JIM GAVULA (R3)
Power Reactor Unit Info
Unit SCRAM Code RX Crit Initial PWR Initial RX Mode Current PWR Current RX Mode
1 M/R N 0 Cold Shutdown 0 Cold Shutdown
Event Text
THE REACTOR WAS MANUALLY SCRAMMED WHILE IN COLD SHUTDOWN.

WHILE PERFORMING CONTROL ROD VENTING WITH THE 24-17 ROD IN POSITION 48, THE TRANSPONDER CARD IN THE ROD CONTROL & INSTRUMENT SYSTEM (RC&IS) FAILED. THE ROD BECAME STUCK IN THIS POSITION, DUE TO THE RC&IS CARD FAILURE, AND THE REACTOR WAS MANUALLY SCRAMMED. THE 24-17 ROD, THE ONLY ONE IN THE OUT POSITION DURING ROD VENTING, WAS FULLY INSERTED AFTER THE SCRAM. THE CAUSE OF THE RC&IS COMPONENT FAILURE IS UNKNOWN AND BEING INVESTIGATED.

THE RESIDENT INSPECTOR WILL BE NOTIFIED.