Forwards LERs 86-002-01,86-003-01 & 86-005-01.Rept date changed to 860213 & nominal expected valve temp changed to 557 F for LER 86-002-00.
Accession Number: ML20211A937
Date Released: Wednesday, August 12, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20211A932 - Forwards LERs 86-002-01,86-003-01 & 86-005-01.Rept date changed to 860213 & nominal expected valve temp changed to 557 F for LER 86-002-00. (2 page(s), 6/4/1986)
- ML20211A952 - LER 86-002-01:on 860114,during performance of preoutage test to verify steam generator safety valve setpoint,3 of 20 valves found w/setpoints outside specified band.Caused by setpoint drift.Valves adjusted & retested. (3 page(s), 6/4/1986)
- ML20211A993 - LER 86-003-01:on 860117,partial failure of planned test of safety injection sys occurred.Caused by wear on relay latching mechanism which reduced clearance between latch screw & latch plate.Screw clearance adjusted. (3 page(s), 6/4/1986)
- ML20211B013 - LER 86-005-01:on 860207,wiring,limit & torque switches in certain motor operators not addressed in environ qualification documentation.Affected wiring,limit & torque switches replaced during outage. (4 page(s), 6/4/1986)