Home > NRC Library > ADAMS Public Documents
Forwards LERs 82-085/03L-0,82-088/03L-0 & 82-089/03L-0.
Accession Number: ML20065D889
Date Released: Thursday, March 19, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20065D885 - Forwards LERs 82-085/03L-0,82-088/03L-0 & 82-089/03L-0. (1 page(s), 9/21/1982)
- ML20065D905 - LER 82-085/03L-0:on 820824,RCS post-reactor trip specific activity samples found greater than Tech Spec limits.Caused by fuel defects in reactor core.Acclerated sampling frequency implemented till RCS activity less than Tech Spec. (5 page(s), 9/21/1982)
- ML20065D914 - LER 82-088/03L-0:on 820826,loop A steam line pressure transmitter (PT-1-474) signal failed high.Cause undetermined.Transmitter removed from instrument loop,bench tested & reinstalled. (2 page(s), 9/21/1982)
- ML20065D923 - LER 82-089/03L-0:on 820826,B core cooling monitor failed, causing spurious alarms.Caused by relay failure on printed circuit cards A-1 & A-2.Boards repaired & core cooling monitor returned to svc. (2 page(s), 9/21/1982)