Forwards LERs 80-028/03L-0,80-029/03L-0 & 80-030/03L-0.
Accession Number: ML19343A219
Date Released: Monday, December 23, 2019
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML19343A218 - Forwards LERs 80-028/03L-0,80-029/03L-0 & 80-030/03L-0. (1 page(s), 9/8/1980)
- ML19343A223 - LER 80-028/03L-0:on 800811,at 100% power,control element assembly 41 dropped from 180 to zero steps.Caused by faulty jumper cable from refuel disconnect panel to reactor head. Power reduced & assembly realigned.Replacement planned. (1 page(s), 9/8/1980)
- ML19343A224 - LER 80-029/03L-0:on 800812,during surveillance test on 12 U diesel,125 VDC ground alarm received.Caused by frayed insulation on wire in Bendix connector allowing contact between bare wire & connector shell.Wire recovered. (1 page(s), 9/8/1980)
- ML19343A226 - LER 80-030/03L-0:on 800812,during routine operation, containment air temp exceeded 120 F.Caused by svc water temp control valve to reactor bldg closed cooling water heat exchangers being set too high.Valve readjusted. (1 page(s), 9/8/1980)