Forwards LERs 80-015/03L-0,80-016/03L-0 & 80-017/03L-0.
Accession Number: ML19312D498
Date Released: Friday, November 22, 2019
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML19312D497 - Forwards LERs 80-015/03L-0,80-016/03L-0 & 80-017/03L-0. (1 page(s), 3/14/1980)
- ML19312D504 - LER 80-015/03L-0:on 800217,after tying main generator onto grid,DEH sys malfunctioned causing load increase,resulting in avg decreasing to 539 F.Cause under investigation.DEH placed in manual to stop load increase. (1 page(s), 3/14/1980)
- ML19312D509 - LER 80-016/03L-0:on 800215,while performing surveillance test procedure FNP-1-STP-22.17,TDAFWP thrust bearing exceeded 160F.Caused by high bearing oil level after maint on thrust bearing.Oiler assembly repositioned. (2 page(s), 3/14/1980)
- ML19312D513 - LER 80-017/03L-0:on 800222,while manually starting turbine driven auxiliary feedwater pump,turbine tripped on overspeed.Caused by limit switch being out of adjustment. Limit switch adjusted & feedwater pump returned to svc. (1 page(s), 3/14/1980)