Forwards LERs 80-002/01T-0,80-003/01T-0,80-004/01T-0, 80-005/01T-0,80-008/01T-0,80-009/01T-0,80-010/01T-0, 80-012/01T-0 & 80-014/01T-0.
Accession Number: ML112900690
Date Released: Thursday, September 15, 2011
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML112900689 - Forwards LERs 80-002/01T-0,80-003/01T-0,80-004/01T-0, 80-005/01T-0,80-008/01T-0,80-009/01T-0,80-010/01T-0, 80-012/01T-0 & 80-014/01T-0. (2 page(s), 4/8/1980)
- ML112900691 - LER 80-002/01T-0:on 800225,during refueling outage,local leak rate for A0-2-86A outboard MSIV exceeded Tech Spec acceptance criteria.Caused by poppet not seating properly. Poppet machined & stem replaced. (2 page(s), 4/8/1980)
- ML112900693 - LER 80-003/01T-0:on 800225,during refueling outage,local leak rate for A0-2-86D,outboard MSIV,exceeded Tech Spec acceptance criteria.Caused by lapping of main seat so that poppet did not seat properly.Poppet machined. (2 page(s), 4/8/1980)
- ML112900695 - LER 80-004/01T-0:on 800223,during local leak rate testing, HPCI-9 turbine exhaust line check valve found leaking in excess of Tech Spec acceptance criteria.Caused by leakage past body-to-seat ring threaded joint. (2 page(s), 4/8/1980)
- ML112900697 - LER 80-005/01T-0:on 800303,during local leak rate testing, XP-6 standby liquid control outboard isolation valve,found leaking in excess of Tech Specs.Caused by accumulation of scale on seat.Replaced valve. (2 page(s), 4/8/1980)
- ML112900699 - LER 80-008/01T-0:on 800303,during local leak rate testing, A0-2896 torus vent isolation valve found leaking in excess of Tech Spec acceptance criteria.Cause undetermined.Valve disassembled,inspected,cleaned & reassembled. (2 page(s), 4/8/1980)
- ML112900701 - LER 80-009/01T-0:on 800306,during refueling outage,local leak rate for RCIC-9 turbine exhaust check valve,exceeded Tech Spec acceptance criteria.Probably caused by downstream check valve jacked shut for test.Valves lapped & retested. (2 page(s), 4/8/1980)
- ML112900702 - LER 80-010/01T-0:on 800324,during local leak rate testing, CV-7956 torus instrument air isolation valve found leaking in excess of Tech Spec acceptance criteria.Apparently caused by dirt on seat.Valve cleaned & reassembled. (2 page(s), 4/8/1980)
- ML112900704 - LER 80-012/01T-0:on 800307,during local leak rate testing, AD-2561A drywell equipment drain sump isolation valve found leaking in excess of Tech Specs.Caused by packing leak. Packing tightened. (2 page(s), 4/8/1980)
- ML112900705 - LER 80-014/01T-0:on 800314,during refueling outage,local leak rate for A0-2-80A inboard MSIV exceeded Tech Spec acceptance criteria.Caused by poppet not seating properly. New poppet & stem installed. (2 page(s), 4/8/1980)