Forwards LERs 95-017-01,95-022-02,96-001-01 & 96-014-01 which has been revised to retract originally proposed CAs that will no longer be implemented as result of util decision to cease operations at plant.
Accession Number: ML20198E920
Date Released: Monday, October 28, 2024
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20198E913 - Forwards LERs 95-017-01,95-022-02,96-001-01 & 96-014-01 which has been revised to retract originally proposed CAs that will no longer be implemented as result of util decision to cease operations at plant. (1 page(s), 8/1/1997)
- ML20198E927 - LER 95-017-01:on 950810,degraded weld was discovered in CAR fan svc water return pipe.Caused by galvanic corrosion. Replaced four dissimilar welds at inlet to throttle valves by installing carbon steel flanges. (3 page(s), 8/1/1997)
- ML20198E937 - LER 95-022-02:on 951215,identified potential that actual post of LOCA low pressure safety injection sys delivery rates may be less than safety analysis assumptions.Caused by sys flow path degradation or pump wear.Assessment performed. (5 page(s), 8/1/1997)
- ML20198E955 - LER 96-001-01:on 960111,determined that high side sensing line of instrument blocked.Caused by blocked sensing line & personnel failure to immediately identify problem w/gauge. Personnel counseled. (3 page(s), 8/1/1997)
- ML20198E962 - LER 96-014-01:on 960726,identified discrepancy in mesh sizing,screen fit-up & method of attachment.Caused by inadequate documentation of addition of screen during const coupled w/general acceptance.Sump screen replaced. (4 page(s), 8/1/1997)