Home > NRC Library > ADAMS Public Documents
Forwards LERs 83-076/03L-0,83-050/03L-0 & 83-051/03L-0.
Accession Number: ML20082H701
Date Released: Sunday, April 5, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20082H695 - Forwards LERs 83-076/03L-0,83-050/03L-0 & 83-051/03L-0. (1 page(s), 11/21/1983)
- ML20082H711 - LER 83-050/03L-0:on 831024,on two occasions,RCS Tavg dropped to 540 F & 539 F,below Tech Spec requirements.Caused by failure to check controller setpoint & withdraw control rods.Operators counseled. (2 page(s), 11/21/1983)
- ML20082H717 - LER 83-051/03L-0:on 831022,train B control room emergency air cleanup sys declared inoperable.Caused by solenoid valve linkage on evaporator line being out of adjustment.Linkage adjusted & solenoid valve replaced on 831102. (2 page(s), 11/21/1983)
- ML20082H720 - LER 83-076/03L-0:on 831022,monthly hydrogen analyzer surveillance of hydrogen recombiner 2B not current,per Tech Specs.Caused by failure to check surveillance record. Recombiner secured on 831022.Personnel counseled. (2 page(s), 11/21/1983)