Home > NRC Library > ADAMS Public Documents
Forwards LERs 83-084/03L-0,83-085/03L-0 & 83-086/03L-0.
Accession Number: ML20080Q492
Date Released: Friday, April 3, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20080Q489 - Forwards LERs 83-084/03L-0,83-085/03L-0 & 83-086/03L-0. (1 page(s), 9/28/1983)
- ML20080Q497 - LER 83-084/03L-0:on 830901,during controlled shutdown at approx 10E-8 power,T average decreased below Tech Spec min of 541 F.Cooldown terminated at 535 F.Temp would not return to 541 F within 15 minutes.Reactor trip breakers opened. (1 page(s), 9/28/1983)
- ML20080Q507 - LER 83-085/03L-0:on 830902,during startup at 20% power,after turbine generator paralleled w/sys grid,generator load increased to prevent motoring,resulting in pressure drop below Tech Specs.Caused by heater breaker trip. (1 page(s), 9/28/1983)
- ML20080Q510 - LER 83-086/03L-0:on 830905,chart paper on containment sump flow monitoring recorder 1CS-001,would not advance.Cause not determined.Chart paper adjusted & recorder verified operable.Design change submitted. (1 page(s), 9/28/1983)