Forwards LERs 83-068/03L-0,83-069/03L-0 & 83-070/03L-0.
Accession Number: ML20080J345
Date Released: Friday, April 3, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20080J343 - Forwards LERs 83-068/03L-0,83-069/03L-0 & 83-070/03L-0. (2 page(s), 9/14/1983)
- ML20080J351 - LER 83-068/03L-0:on 830815,while in Mode 5,alarms on fire detection Zones 136 & 141 would not clear.Caused by dust &/or welding fumes associated w/removal of valve 1NC-18. Alarms reset. (1 page(s), 9/14/1983)
- ML20080J360 - LER 83-069/03L-0:on 830815,while in Mode 5,trouble alarm for fire detection Zone EFA 72 would not reset.Caused by water & dirt accumulation on underside of 733 floor/716 ceiling.Detector & base contacts cleaned. (1 page(s), 9/14/1983)
- ML20080J364 - LER 83-070/03L-0:on 830815,while in Mode 5,trouble alarm for fire detection Zone EFA 131 would not reset.Caused by incorrect installation of resistors for rate-of-rise detectors.Resistors rewired properly. (1 page(s), 9/14/1983)