Forwards LERs 82-014/03L-0,82-009/03L-0,82-010/03L-0, 82-012/03L-0 & 82-015/03L-0.
Accession Number: ML20071H295
Date Released: Wednesday, March 25, 2020
Package Contents
The following links on this page are to Adobe Portable Document Format (PDF) files. To obtain a free viewer for displaying this format, see our Plugins, Viewers, and Other Tools.
- ML20071H293 - Forwards LERs 82-014/03L-0,82-009/03L-0,82-010/03L-0, 82-012/03L-0 & 82-015/03L-0. (1 page(s), 2/26/1982)
- ML20071H301 - LER 82-014/03L-0:on 820127,amp readings for heat tracing panel 8,circuit 2B found below acceptance criteria.Caused by excessive heat tape.Defective heat tracing replaced. Manner in which borated lines are heat traced changed. (2 page(s), 2/26/1982)
- ML20071H303 - LER 82-009/03L-0,on 820128,inadequate svc water flow resulted in higher 2-CH-P-1C lubricating oil temp.Pump declared inoperable.Caused by foreign object in svc water temp control valve body.Object removed. (2 page(s), 2/26/1982)
- ML20071H312 - LER 82-010/03L-0,on 820129,during 100% power following refueling,protection channels I & III indicated only 93%. Apparently caused by mod to RTD bypass lines.Precision calorimetric performed & Delta T summators adjusted. (2 page(s), 2/26/1982)
- ML20071H318 - LER 82-012/03L-0,on 820131,amp readings for heat tracing circuits 23A & C on panels 8 & 9 found below acceptance criteria.Apparently caused by inadvertent damage to heat tracing tape during cleanup operations.Tape replaced. (2 page(s), 2/26/1982)
- ML20071H328 - LER 82-015/03L-0,on 820129,while performing PT-33,low control room envelope pressure of .045 inches of water found.Caused by deterioration of weather stripping around doors.Weather stripping replaced. (2 page(s), 2/26/1982)